Click a module from the list to access setup of the module. The green/grey light indicates if connection to the
module is established.
7. Manually select how many devices are connected
8. List of modules
The module ID must correspond with the ID selected on the module and can be changed manually in the list.
The fail class and delay set here are triggered if the specific module is missing.
The first time you open the menu, the buttons will be inactive and it is necessary to read the
configuration from the controller.
If the communication to a CIO 116 or CIO 308 module is lost, the AGC will continue with the last
received input value.
3.1.1 Step-by-step guide to setting up communication the first time
Follow these steps to establish communication to the CIO modules. Setup of the I/Os is described in a later
chapter.
●
Adjust the ID from 1-15 on the switch by rotating the screw in the lower left corner
●
Select which CAN port to use for CIO (parameter 7840).
Select "Ext. modules DEIF" if the CAN port is only used to CIO modules, but If an engine (ECU)
also is connected to the CAN line then "H5 EIC" or similar should be selected.
●
Enable CIO communication (parameter 7890).
●
Open the CIO menu by pressing the CIO icon
●
Read the configuration from the controller.
●
Auto-detect the number of modules and their ID.
This only works if the CIO modules are connected, but it is also possible to manually add and
configure modules by changing value in "Amount of CIO xxx modules"
●
Determine fail class for module missing for all modules.
●
Write the configuration to the controller.
3.1.2 Step-by-step guide to update firmware to CIO module
Follow these steps to update the firmware for a CIO module.
●
Apply power to the module
●
Set ID to 0.
●
Connect a USB cable between the CIO module and a PC
●
Open the utility software and connect to the CIO module via USB.
●
Login as "Customer" with the password 2000.
●
Write a new firmware to the device by pressing this icon
●
When the firmware is completed, the connection can be stopped
, the USB cable can be removed, and
the ID should be returned to the desired ID.
CIO 308 installation and commissioning
guide 4189341078 UK
Communication
DEIF A/S