2.4.2 CIO 308 wiring
1 2 3 4 5 6 7
A
CANbus
Status
Max 1A
Supply
+ -
C
om
L
H
8
0
4
12
ID selector
CIO 308
DEIF
LED1
LED2
S1
Firmware
8 Multi Inputs
LED1:
Red – Device failure
Green – Status output
LED2:
Red – Comm. failure
Green – Comm. OK
S1:
CANbus End resistor
8
9
10
11
12
13
14
15
16
17
18
19
B
C
I
8
A
B
C
I
11
A
B
C
I
14
A
B
C
I
17
A
B
C
I
20
A
B
C
I
23
A
B
C
I
26
A
B
C
I
29
20
21
22
23
24
25
26
27
28
29
30
31
12/24 V DC
-
+
Sensor
Sensor
Sensor
Sensor
Sensor
Sensor
Sensor
Sensor
DEIF
recommends
grounding one of
the C terminals
PT100/1000 2-wire
A
B
C
PT100/1000 3-wire
A
B
C
RMI 2-wire or 3-wire
A
B
C
RMI 1-wire
A
B
C
R
R
Digital Input
A
B
C
Thermocouple
A
B
C
R
+
-
Current 4-20 mA
A
B
C
Voltage 0-10V DC
A
B
C
I
+
-
+
- V
When thermocouples and Pt100/ Pt1000 sensors are used, it is recommended to connect one
of the C terminals to Earth (all C terminals are internally connected). It will minimise noise and
sensitivity if touching terminals when measuring.
Twisted pair or/and shielded cable on input, is recommended to achieve specified accuracy
and for optimisation of immunity-noice.
CIO 308 installation and commissioning
guide 4189341078 UK
Installation, mounting and wiring
DEIF A/S
Page 11 of 25