5.4.2 CAN bus engine communication
Recommended cable: Belden 3105A or equivalent, 24 AWG (0.5 mm
2
) twisted pair, shielded, impedance 120 Ω, <40 mΩ/m, min. 95
% shield coverage.
In order to be EN60255 compliant, when wiring is more than 10 m, terminal 28 must be connected to GND.
5.4.3 Modbus
1
A
1
G
N
D
1
B
2
A
2
G
N
D
2
B
3
3
3
4
3
5
3
6
3
7
3
8
Scada/PLC/
...
120
Scada/PLC/
...
120
Recommended cable: Belden 3105A or equivalent, 24 AWG (0.5 mm
2
) twisted pair, shielded, impedance 120 Ω, <40 mΩ/m, min. 95
% shield coverage.
In order to be EN60255 compliant, when wiring is more than 10 m, the terminals 34 and 37 must be connected to GND.