5.2.2
Gas supply
Before mounting, check that the gas meter has sufficient capacity (in
m
3
/h). To do this, you should bear in mind the consumption of all
appliances. If the capacity of the gas meter is too low, inform the gas
supply company.
The boilers are preset to run on G20 gas (gas H) and can be adapted to
run with the following gases:
G25 (gas L),
G31 (gas P),
Important
To use a different type of gas, contact an approved assistance
service.
5.2.3
Electrical power supply
Power supply voltage
230 V AC/50 Hz
Caution
Please ensure the polarities shown on the terminals are followed,
i.e live (L), neutral (N) and earth (
)
5.2.4
Circulating pump
The boiler's water flow rates must be higher than or equal to the
specifications in the table below:
Tab.14 Water flow rates in the boiler
Working flow rate
with the low-loss
header kit
Unit
IX 145–50
IX 145–70
IX 145–90
IX 145–110
Minimum flow rate
litres/hour
800
1500
2000
2250
Maximum flow
litres/hour
2450
3500
4600
4800
1 Q flow rate (litres/hour)
2 {3}H pressure in metres of water column (mWC)
3 Operating water flow rate at nominal heat output = 1330 litres/hour
where ∆T = 30 °C
4 Operating water flow rate at nominal heat output = 2000 litres/hour
where ∆T = 20 °C
5 Operating water flow rate at nominal heat output = 2660 litres/hour
where ∆T = 15 °C
ΔT Temperature difference between the flow water and the return
water in the boiler
Fig.17
Pressure drops for IX 145–50
MW-3000007-01
2
4
6
8
10
12
0
1
0
0
0
5
0
0
1
5
0
0
2
0
0
0
2
5
0
0
3
0
0
0
2
3
1
4
5
5 Before installation
7702703 - v04 - 05092019
IX
27
Содержание IX 145-110
Страница 130: ...15 Disposal recycling 130 IX 7702703 v04 05092019 ...