23 

 

  

5.2.2. Electric Connection 

 

Electrical  installation  must  be  done  by  authorized  person  according  to  device 

capacity  and  with  suitable  diameter  cable.  Electric  of  device  must  have  suitable 

specification for for cut off device power and residual current device that has amper 

value and fuse separately. Fuse must be near to device. Grounding of device must 

absolutely be done. If there is not grounding at the place that the device is installed, 

grounding  must  be  made  for  device  by  authorized  person.  Operative  of  grounding 

must  be  controlled  in  determined  periods.    Fuse  must  locate  near  the  device  and 

device  cable  must  not  be  strained  while  connect  to  fuse.  Connection  of  cables  to 

fuse must be made by authorized person.    

 

 

 

 
 
 
 

 
 

 

Cable  diameter  that  is  calculated  according  to  device  capacity  and  cable  length, 

residual current device and fuse amper values can be seen at the following table.  

 

 

Make sure that cables are connected to correct places

 

 

 

 Loose cable connections can be caused to accident

 

Содержание UKDAX-10EBT

Страница 1: ...1...

Страница 2: ...d to device with suitable cable section determined inside this manual Residual Current Device and grounding must definitely place Installation of the device must not be made to humidity places and pla...

Страница 3: ...asing boiler temperature 65C once a day If the device will not have used for a long time perform following points are suggested Bring switch of the device OFF position Close taps both heating and hot...

Страница 4: ...cts that affect air flow must be positioned properly For sensing room thermostad ambient temperature correctly that it placed it should be positioned far and proper height from window object or heat s...

Страница 5: ...5 3 CONFIGURATION OF THE DEVICE Wall Type Boiler With Tank Floor Type Boiler With Tank...

Страница 6: ...6 Wall Type External Boiler With Tank...

Страница 7: ...Weight Without Water Boiler Kg Volume l 3 400 V 50 Hz Electrical Boiler With Tank UKDAX 10EBT 10 50 UKDAX 12EBT 12 50 UKDAX 16EBT 16 52 50 UKDAX 18EBT 18 52 UKDAX 20EBT 20 52 UKDAX 24EBT 24 52 1 220...

Страница 8: ...BT 16 120 105 1152 600 590 UKDAX 120Y18BT 18 120 105 1152 600 590 UKDAX 120Y20BT 20 120 105 1152 600 590 UKDAX 120Y24BT 24 120 105 1152 600 590 1 220 V 50 Hz Electrical Boiler With Tank UKDAX 80Y10BM...

Страница 9: ...32 2 12 UKDAX 36HBT 36 700 450 320 35 4 12 UKDAX 40HBT 40 700 450 320 35 4 12 UKDAX 48HBT 48 700 450 320 35 4 12 1 220 V 50 Hz Electrical Boiler With External Tank UKDAX 6HBM 6 700 400 220 23 5 7 UKD...

Страница 10: ...10 5 INSTALLATION OF DEVICE Wall Type Boiler With Tank Device installation must be done by authorised personnel...

Страница 11: ...11 Floor Type Boiler With Tank UKDAX 80YxxBT UKDAX 80YxxBM Simge a b c d e f g h l mm 600 836 84 149 214 84 186 590...

Страница 12: ...12 Floor Type Boiler With Tank UKDAX 120YxxBT UKDAX 120YxxBM Simge a b c d e f g h l mm 600 1152 84 149 214 84 186 590...

Страница 13: ...13 Installation Of Floor Type Boiler With Tank UKDAX 80YxxBT UKDAX 80YxxBM...

Страница 14: ...14 UKDAX 120YxxBT UKDAX 120YxxBM...

Страница 15: ...15...

Страница 16: ...16 Wall Type Boiler With Tank Kapasite a b c d e f g h i j k l 10 24 KW 700 400 220 58 122 277 342 65 200 123 100 200 30 48 KW 700 450 320 83 147 302 367 75 225 148 100 225 l ler mm cinsindendir...

Страница 17: ...17 Plumbing Connection Diagram Of External Boiler With Tank...

Страница 18: ...on the cooker or similar cooking devices Do not leave combustion products inside device installed room Heating sensitive walls for example wooden walls must be protected with steady insulation Before...

Страница 19: ...ect that system pressure is over 6 bar install pressure reducer to inlet of device or flat entrence Device installation place must be far way from blockers obstruction parts and bulges during repairin...

Страница 20: ...he device tightly If necessary screw the hanger plate in more point Hold the device by two people opposite to each other place it on the hanger plate fixed to the wall Do not leave the device without...

Страница 21: ...t be silt trap at inlet part between valve and device Valve and still trap must be used at boiler cold water inlet 5 2 1 1 Boiler Filling After installment is completed boiler is needed to fill This p...

Страница 22: ...side radiators by opening air relief cock placed in side of radiators and close when water starts to flow When the accumalted air inside radiators discharge it can be decrease at heating system water...

Страница 23: ...ounding at the place that the device is installed grounding must be made for device by authorized person Operative of grounding must be controlled in determined periods Fuse must locate near the devic...

Страница 24: ...2 5 4 20 3 400 3 30 4 3 40 5 6 24 3 400 3 36 4 3 50 5 6 30 3 400 3 45 5 3 63 5 10 36 3 400 3 54 6 3 63 5 10 40 3 400 3 60 7 3 63 5 16 48 3 400 3 72 8 3 80 5 16 1 220 V 50 Hz 6 1 220 27 3 32 3 4 10 1 2...

Страница 25: ...Floor Heating Indicator Days Of Week Time Programming Can be made 7 pcs time programming Hour Capacity Indicator Ready to operation Indicator Hot Water Heating Indicator Radiator Heating Indicator Res...

Страница 26: ...Before operating the device suitability of all mechanic and electrical connections must be controlled Boiler and heating system must be completely filled and radiator vent must be done Our company is...

Страница 27: ...FF When it is ON again starts to operate with same settings When operation off device is set as boiler and radiator heating before OFF position if boiler temperature is lower than set temperature devi...

Страница 28: ...temperature is lower than set temperature device operates for boiler heating and symbols are seen with shower expressions symbol blinks If boiler temperature is equal or more than the set temperature...

Страница 29: ...knob For long time pressing knobs forexample 2 3 seconds before hearing warning warning beep it does not mean pressing knob 6 4 Operation Parameter Setting 6 4 1 Day and Hour Setting Switch Off the d...

Страница 30: ...30 Days are set by pressing with one second intervals to or buttons Press button hour blinks By pressing or one second interval hour is set between 0 and 23...

Страница 31: ...31 Press button minute blinks By pressing or button one second interval min set between 0 and 60 By pressing button or if not pressing any button for a 10 sec exit from setting menu by saving settings...

Страница 32: ...or boiler heating device operation mode must be changed as radiator heating for setting radiator temperature At the end of the process device must be taken to previous operation mode Check 6 4 8 After...

Страница 33: ...33 Boiler temperature setting and symbols are seen at LCD Display When symbol blinks when device operates for boiler heating setting can be made between 30 oC ile 65 oC by pressing or...

Страница 34: ...ng for setting temperature of boiler it is needed to change operation mode of the device as boiler heating At the end of this process device must be taken to previous operation mode Check 6 4 8 After...

Страница 35: ...35 After device heats the boiler it operates for radiator heating Boiler heating starts again when decreases 7C from set temperature...

Страница 36: ...e difference between Heating exit and Heating return of device can be set While the device is in normal operation mode Enter setting menu by pressing 2 3 seconds Press the button one second interval u...

Страница 37: ...6 4 5 Room Thermostad Setting It is possible to command device with room thermostad In this way device operates according to temperature of environment of room thermostad place Room thermostad tempera...

Страница 38: ...to floor heating mode by authorized services at the time of first operation In this way in this case it will be impossible to change heating mode for users by consciously or by mistake For radiator he...

Страница 39: ...39 0 is chosen with or symbols for floor heating mode...

Страница 40: ...finitely temperature must not set over 55C for floor heating systems In case of setting our companies is not responsible from damages or accidents that may occur For floor heating systems because of h...

Страница 41: ...s full capacity Forexample if the device is 24kw P1 8 KW P2 16kw P3 24 KW While device operates regularly Enter setting menu by pressing button 2 3 seconds Press one second interval until is seen With...

Страница 42: ...42 Exit menu by pressing button 6 4 8 Operation Mode Setting Device can operate 3 different operation mode Radiator Operating Mode Device only makes radiator heating boiler heating does not occur...

Страница 43: ...h radiator heating and boiler heating Priority is always for boiler heating While radiator heating is being done if it is needed boiler heating device stops radiator heating and operates for boiler he...

Страница 44: ...e is chosen If heating is chosen device only operates for radiator heating If shower is chosen device operates for boiler heating If heating and shower are chosen at the same time device operate for b...

Страница 45: ...ring program and the T temperature difference can be adjusted If the programming has been made and activated the device will not be heated during periods of time that are not programmed Device waits a...

Страница 46: ...46 Press button one second interval until Timing Time Phase is seen Timing program blink By pressing or buttons timing program is chosen between 1 and 7 Press button...

Страница 47: ...t stays at OFF position can not be entered to timing program By pressing button week day days are chosen With or buttons intended week day or days can be chosen Week days are group as in the following...

Страница 48: ...48 Weekends SUN SAT Weekdays MON TUES WED THUR FRI Days can be chosen one by one...

Страница 49: ...49 Press button program start hour blinks With or buttons program start hour is determined Press button Program start minute blink...

Страница 50: ...50 With or buttons program start minute is determined Press button Program finish hour blink With or buttons program finish hour is determined...

Страница 51: ...51 Press button Program finish min blink With or buttons program finish minute is determined Press button Temperature indicator blink...

Страница 52: ...of intendent program is chosen with or buttons Press button symbol and exit return temperature difference adjustment indicator blink Intendent T exit return temperature difference at selected program...

Страница 53: ...ams are not necessary You can set time programs between 1 and 7 as much as you want Because of unadjusted programs remain OFF position they will not be active After programming is finished when it is...

Страница 54: ...pressing button 2 or 3 seconds By activating electric supply device will be protected by following steps Freezing Prevention Function If temperature of water inside device reduces under 5C device ope...

Страница 55: ...t time once every 18 hrs 6 5 2 Long Term OFF If you do not operate the device for a long time make the circuit breaker OFF after pressing button 2or 3 seconds In this case because of freezing preventi...

Страница 56: ...56 7 ELECTRIC DIAGRAM...

Страница 57: ...ges and accidents 9 TROUBLE SHOOTING Ar za Kodu Ar za z m E0 Water pressure is not enough Set the water pressure between 1 and 2 bars Water pressure switch damage Call authorized service Although you...

Страница 58: ...58 Pipe is blocked or valve is closed Control if tis closed valve or not at heating installation and clean silt trap E5 Pump damage Flowmeter damage Call the authorized service...

Страница 59: ...Not proper connections Sealing Gasket is damaged Connections must be made again Renew the sealing gasket Keyboard Damage PCB Damage Call authorised service Unproper Cable Using Loose Connection Turn O...

Страница 60: ...ited irketi Nam k Kemal Mah Marmara Cad No 74 mraniye stanbul Tel 90 216 369 85 36 37 Fax 90 216 385 95 45 E Mail info daxom com Merkez Servis Nam k Kemal Mah Marmara Cad No 74 mraniye stanbul Tel 902...