Datel muRata PS DMS-40LCD-4/20S Series Скачать руководство пользователя страница 3

DMS-40LCD-4/20S Series

Ultra-Low 2.9V Loop-Drop 4½ Digit 

LCD Display Process Monitor

Technical enquiries

 email: [email protected], tel: 

+1 508 339 3000

www.murata-ps.com

MPM_DMS401LCD-420S.D01      

Page 3 of 5

OPERATING AND SETUP INSTRUCTIONS

 

Switch S2

 

SW3 

  SW4 

SW5 

SW6

 

 

DP1 

  DP2 

DP3 

DP4

The following procedure must be performed as the first re-calibration step 
every time DIP-switches S1 and S2 are reconfigured to select a new display 
range. The following procedure assumes the DMS-40LCD-4/20S is initially 
completely mis-adjusted, i.e., both potentiometers and DIP-switches S1 and 
S2 are randomly set. Make sure that all DIP-switch actuators are pushed as 
far as they will go to their designated ON (closed) or OFF (open) positions.

1.

  Set R7 (gain/span adjust) and R3 (zero/offset adjust) fully clockwise, 

roughly 20 turns, then using the settings found in the  

selected 

range, place the DIP-switches on S1 and S2 to the appropriate positions 
for the desired display reading.

2.

  Apply a precision 4mA input with proper polarity and adjust R3  

 (top 20-turn potentiometer) until the meter’s display reads “0000”.

3.

  Apply a precision 20mA input and adjust R7 (bottom 20-turn potentiom-

eter) until the display reads the maximum desired reading. Repeat steps 
2 and 3 to make sure the adjustments did not affect one another.

4.

  If necessary, select the appropriate decimal point by setting either  

 SW3, SW4, SW5, or SW6 of S2 to ON (DP1, DP2, DP3, or DP4,  
 respectively.

NOTE:

 Please keep in mind the transmitter’s 4mA and 20mA output accu-

racy may affect display readings which are at, or very close to, the high and 
low limits of the selected range. See Example #2 below and Technical Note 1 
for more information). 

Examples

The examples below illustrate how to configure the meter to perform some 
typical measurements. Recall that R3 and R7 must be set to their full clock-
wise position before calibrating the meter.

1.

  Desired display readings are: 

 

 

4mA = “0.000” 

 

 

20mA = “3.000”

Use DIP-switch setting #3 in Table 1 and enable decimal point DP2  
by placing SW4 of switch S2 to ON. Apply 4mA and adjust R3 so the display 
reads “0.000”. Apply 20mA and adjust R7 so the display reads “3.000”.

2.

  Desired display readings are:

 

 

4mA = “0000” 

 

 

20mA = “8600”

Use DIP-switch setting #11. Apply 4mA and adjust R3 so the display reads 
“0000”. Apply 20mA and adjust R7 so the display reads “8600”. If the trans-
mitter’s full-scale output is less than 20.0mA, it may not be possible to adjust 
R7 for a reading of “8600” with setting #11. If this occurs, select setting #12 

ON

ON

1

1

1

2

3

4

5

6

2

3

4

5

6

1

2

3

4

ON

ON

ON

1

1

1

2

3

4

5

6

2

3

4

5

6

1

2

3

4

ON

S1 

 

S2

S1 

 

S2

ON

ON

1

1

1

2

3

4

5

6

2

3

4

5

6

1

2

3

4

ON

S1 

 

S2

Table 1. DIP-Switch Settings 

ON

ON

1

1

1

2

3

4

5

6

2

3

4

5

6

1

2

3

4

ON

S1 

 

S2

and re-calibrate both R3 and R7 to obtain “0000” and “8600”. Note that 
for these display readings no decimal points are used. Set SW3, SW4, 
SW5 and SW6 of switch S2 to OFF. 

3.

  Desired display readings are:

 

 

4mA = “0000” 

 

 

20mA = “10000”

Use DIP-switch setting #13. Apply 4mA and adjust R3 so the display 
reads “0000”. Apply 20mA and adjust R7 so the display reads “10000”. 
For these display readings no decimal points are used. Set SW3, SW4, 
SW5 and SW6 of switch S2 to OFF. 

4.

  Desired display readings are:

 

 

4mA    = “.0000” 

 

 

12mA  = “.2500”

This example is not as straightforward as the previous three. Notice that 
12mA is exactly halfway between 4mA and 20mA. If we assume the 
input could go up to 20mA, the display reading would then be 2 x .2500 
or “.5000”. From Table 1, select DIP-switch setting #7 and enable DP1 
via SW3 of switch S2. Apply 4mA and adjust R3 so the display reads 
“.0000”. Apply 12mA and adjust R7 so the display reads “.2500”.

Switch S1

Switch S2

Display Reading

SW1 SW2 SW3 SW4 SW5 SW6 SW1 SW2

4mA

20mA

01.

0000

2250-2450

OFF

ON

ON

ON

OFF

OFF

ON

ON

02.

0000

2450-2800

OFF

ON

ON

ON

OFF

OFF OFF

ON

03.

0000

2800-3200

OFF

ON

ON

ON

OFF

OFF

ON

OFF

04.

0000

3200-3850

OFF

ON

ON

ON

OFF

OFF OFF OFF

05.

0000

3850-4250

ON

OFF

ON

ON

OFF

OFF

ON

ON

06.

0000

4250-4800

ON

OFF

ON

ON

OFF

OFF OFF

ON

07.

0000

4800-5500

ON

OFF

ON

ON

OFF

OFF

ON

OFF

08.

0000

5500-6200

ON

OFF

ON

ON

OFF

OFF OFF OFF

09.

0000

6200-6750

OFF

OFF

ON

ON

ON

OFF

ON

ON

10.

0000

6750-7700

OFF

OFF

ON

ON

ON

OFF OFF

ON

11.

0000

7700-8600

ON

ON

OFF

ON

ON

OFF

ON

ON

12.

0000

8600-9800

ON

ON

OFF

ON

ON

OFF OFF

ON

13.

0000

9800-10900

ON

ON

ON

OFF

OFF

ON

ON

ON

14.

0000

10900-12000 ON

ON

ON

OFF

OFF

ON

OFF

ON

15.

0000

12000-12800 ON

OFF

OFF

ON

OFF

ON

ON

ON

16.

0000

12800-14000 ON

OFF

OFF

ON

OFF

ON

OFF

ON

17.

0000

14000-15300 ON

OFF

ON

OFF

ON

ON

ON

ON

18.

0000

15300-16300 ON

OFF

ON

OFF

ON

ON

OFF

ON

19.

0000

16300-17600 OFF

OFF

ON

OFF

ON

ON

ON

ON

20.

0000

17600-19999 OFF

OFF

ON

OFF

ON

ON

OFF

ON

Отзывы: