4-3
Logic configuration
The SG-ONE offers 8 types of logic, and by performing the logic configuration procedure listed
below, you can enable the desired logic.
The SG-ONE can transition to the Configuration state from the Run or Protection state.
Configuration operations are disabled in the Initial and Stop states.
Once any logic is configured, it is kept in the SG-ONE even if the power is turned off.
The logic and timer settings can be configured at the same time. Confirm the configuration
methods, and configure the logic and timer properly.
The logic switch is set “1” at the factory. When initially powering on the SG-ONE, thoroughly
confirm the configuration and the operation.
1. Open the protective cover
.
Open the cover to a position that enables you to
set the configuration operations.
Refer to "Using the protective cover" for details.
2. Select the logic switch.
Select and operate the logic switch. When
operating the logic switch, use the attached
configuration tool.
When the logic configuration is changed, "C" is
displayed in the error LED display and the new
number of the logic configuration blinks in the
logic LED display.
If any logic switch is not selected or multiple logic
switches are selected, "E" is displayed in the logic
LED display.
LOGIC No.
TIMER (S)
ENTER
0 .1 .5 1 2 5 15 30
1 2 3 4 5 6 7 8
0 .1 .5 1 2 5 15 30
SAFE-IN
TIMER(S)
SAFE-OUT
SOLENOID
-OUT
START-IN
X0
X1
X2
X3
X4
X5
X6
X7
X10
X11
X12
X13
X14
X15
X16
X17
Y0
Y1
Y2
Y3
Y17
Y20
LOGIC ERROR
LOGIC No.
TIMER (S)
ENTER
0 .1 .5 1 2 5 15 30
1 2 3 4 5 6 7 8
0 .1 .5 1 2 5 15 30
SAFE-IN
TIMER(S)
SAFE-OUT
SOLENOID
-OUT
START-IN
X0
X1
X2
X3
X4
X5
X6
X7
X10
X11
X12
X13
X14
X15
X16
X17
Y0
Y1
Y2
Y3
Y17
Y20
LOGIC ERROR
Configuration tool
LOGIC No.
TIMER (S)
ENTER
0 .1 .5 1 2 5 15 30
1 2 3 4 5 6 7 8
0 .1 .5 1 2 5 15 30
SAFE-IN
TIMER(S)
SAFE-OUT
SOLENOID
-OUT
START-IN
X0
X1
X2
X3
X4
X5
X6
X7
X10
X11
X12
X13
X14
X15
X16
X17
Y0
Y1
Y2
Y3
Y17
Y20
LOGIC ERROR
Fig. 4.1 Normally switch configuration
and LED indication (Run state)
Fig. 4.2 Logic switch is not selected
(Configuration state)
Fig. 4.3 Logic number “7” is selected
(Configuration state)
(Blinking)
(Blinking)
Содержание SG EASY One
Страница 1: ...Safety Control Unit INSTRUCTION MANUAL...
Страница 12: ...2 2 Dimensions 120 0 1 7 1 5 133 5 113 5 122 0 109 5 114 5 72 0 Locking hole Detail of locking hole...
Страница 34: ......
Страница 70: ...5 28 Using an DATALOGIC AUTOMATION light curtain SE series as S1 S2...
Страница 71: ...5 29 Timing chart Logic 3...
Страница 74: ...5 32 Logic circuit Logic 4...
Страница 80: ...5 38 Timing chart Logic 4...
Страница 81: ...5 39...
Страница 103: ...5 61 Operation example Logic 7 Machine running Machine stop danger zone A Movable guard A is opened...