C-BOX 400/410
2
M12 external male connector pinout
Pin Name
Function
1 Shield/Drain
Shield
2
V+
Bus power supply
3 V-
Bus
reference
4
CAN_H
CAN bus data line - H
5
CAN_L
CAN bus data line - L
2.5.3
Connection to a DeviceNet Network
The following figure shows a DeviceNet layout with C-BOX 4X0 devices connected to
a DeviceNet Master:
DeviceNet
Slave node #1
(MAC ID #1)
DeviceNet
Master
DeviceNet
Slave node #2
(MAC ID #2)
DeviceNet
Slave node #n
(MAC ID #n)
C-BOX 4X0
Figure 12 - DeviceNet Connection
It is recommended to use only commercially available DeviceNet connectors for
connecting to the bus. If the C-BOX is installed at the beginning or end of the
DeviceNet cable segment, it is recommended to use DeviceNet connectors, which
contain an integrated terminating resistor.
To ensure that the C-BOX functions without errors, the shield of the DeviceNet cable
must be grounded.
– Ensure that the DeviceNet connector uses the pin assignments shown in par.
– Attach the DeviceNet connector by screwing it onto the DeviceNet interface socket
on the C-BOX 4X0.
14