MA1044 MAQ20-RTD31/-RTD41 Hardware User Manual
Page 26 of 38
Write to register address 8000+124 = 8124 a data value of 8 to set the Average Weight
Read from register address 8000+1034 = 9034 the min data from Channel 4
Read from register address 8000+1054 = 9054 the max data from Channel 4
Read from register address 8000+1074 = 9074 the average data from Channel 4 with weight 8
Read from register address 8000+1130 to 1137 = 9130 - 9137 the last 8 readings from Channel 4
18.0 Reset Functions
Two types of firmware reset are supported in the MAQ20 I/O modules:
Standard Reset
is used to put the module in a user-defined state. The parameters listed below will
be set to the last state saved to EEPROM.
Reset-to-Default
reverts the module to the settings used at the factory during manufacture. It
performs the standard reset actions plus resets most non-volatile parameters to default settings.
Parameters stored in EEPROM are not affected.
Table 2 shows what parameters are affected for each reset.
Table 12: Standard Reset & Reset-to-Default
RESET TYPE
PARAMETERS
Standard Reset
Disables all Alarms, Clears Alarm Status
Resets Alarm Configuration, Limits, and
Deadbands to values stored in module memory
Resets Data Minimum to
–f.s., Data Maximum to
+f.s. and Average Data to 0
Resets Input Range and Average Weight to values
stored in module memory
Clears all Status and Diagnostic registers
Reset-to-Default
Disables all Alarms, Clears Alarm Status
Resets Alarm Configuration, Limits, and
Deadbands to factory default
Resets Data Minimum to
–f.s., Data Maximum to
+f.s. and Average Data to 0
Resets Input Range and Average Weight to
factory default
Clears all Status and Diagnostic registers