EXPANDED DAP4 CONVERSION KIT 

INSTALLATION INSTRUCTIONS 

 
The purpose of this document is to guide the removal of obsolete Mini-DAP (I, II, or III) controllers from 
Data Aire evaporator ceiling equipment, and replacement with current controller model Expanded dap4. 
 
Visit our website to find additional controller documentation resources: 
 

 

System Controls Website 

  

 

 
1.

 

Turn the unit power off. 

2.

 

Unplug the existing Mini-DAP (II & III) controller’s cable. 

3.

 

Disconnect and remove the old wall-mounted controller display.  If the controller model is a Mini‐
DAP III, remove the unit-mount control module along with its mounting brackets. 

4.

 

Disconnect the existing controller’s cable from the terminal strips inside the electrical panel, and 
remove this cable from the unit. 

5.

 

Disconnect  and  remove  the  existing  temperature  and  humidity  sensor,  which  is  either  unit-
mounted in the return air section or remote-mounted in the control space. 

6.

 

Mount the new Expanded dap4 controller outside the unit on skin panels of the unit where space 
is available.  If the existing controller panel is a Mini‐DAP III, mount the Expanded dap4 controller 
in the same location of the existing controller.   

7.

 

Route the Expanded dap4 cable through the same opening of the existing controller’s cable to the 
unit’s electrical panel.  Connect the Expanded dap4 wiring harness to the existing unit’s terminal 
strips.  The wire numbers of the Expanded dap4 wiring harness should line up with the existing 
terminal strip’s pin numbers.  Refer to the conversion wiring diagram for wiring details. 

8.

 

Install the new remote-mount combination temperature and humidity sensor either to the same 
location  of  the  wall‐mount  controller  display  or  to  the  same  location  of  the  existing  sensors.  
Otherwise the sensor will be replaced in the unit’s return air section.  Connect the temperature 
and humidity sensor to the Expanded dap4 controller (J2 and J3 connections).  Refer to conversion 
wiring diagram for wiring details. 

9.

 

Install  the  remote  wall‐mount  controller  display  to  the  same  location  of  the  existing  Mini‐dap 
display. 

 

Disconnect all power to the unit.  Use lock-out tag-out protection; use a multi-
meter to verify no power is being distributed to the equipment. 