background image

 

 

Item # 

OBL-00-008 

Rev. 10-2017 

Copyright ©2017 Danver, Inc. 

 

 

 

INSTALLATION INSTRUCTIONS 

PART 1: Planning the Installation 

 

CAUTION: 

1.

 

For general ventilating use only.  Do not use to exhaust hazardous or explosive materials 

and vapors. 

2.

 

To reduce the risk of fire and to properly exhaust air, the hood must be exhausted to 

outside air.  Never exhaust into a wall, an attic or a concealed area in the building.  This 

can create a potential hazard. 

3.

 

Consult a licensed ventilation contractor or qualified technician for proper installation of 

exhaust ducting. 

Code requirements must be observed whenever outdoor built-in gas appliances are installed.  

Consult with local codes and ordinances regarding the application of your covered, outdoor 

ventilation hood. 

4.

 

Locate the cooking area for minimum cross drafts, when possible. 

5.

 

Ducts must be of adequate size and duct runs should be as short as possible.  Where turns 

are necessary, keep turning radius as large and as smooth as possible. 

6.

 

The ducting must be air tight.  Use a minimum of 2 sheet metal screws at every duct joint.  

Then, seal the duct joints with high quality duct tape. 

7.

 

Only use ductwork constructed of materials deemed acceptable by state, municipal and 

local codes. 

8.

 

Plan the installation so that all minimum clearances are met or exceeded.  Dimensions 

shown provide minimum clearances, unless otherwise specified. 

 

IMPORTANT:

 If the DANVER® DOHC Series Range Hood is installed as a liner for a wood hood, 

proper installation of the hood as a liner is directly related to the material from which the 

custom canopy is constructed.  You must provide structural framing and tight backing in the 

areas in which you are securing the hood inside your custom canopy.  Failure to do so could 

distort and damage the hood and void the warranty. 

 

WARNING!

  Following Are Manufacturer’s Suggestions.  Always Observe Local Building Codes. 

Hoods installed in custom canopies constructed of combustible materials should be installed 

with the combustible material structure a minimum of 36” above the cooking surface.  Hoods 

installed in custom canopies constructed of non-combustible materials, should be installed 

with the non-combustible material structure a minimum of 30” above the cooking surface.  

Follow all instructions regarding minimum safe clearances and installation location.  Failure to 

do so may result in a safety hazard or fire.  To reduce the risk of fire use only metal ductwork. 

 

 

 

Содержание 1300 CFM DOHC Series

Страница 1: ...be completed by a qualified installer Failure to properly install this product may void the warranty Please be advised that the DANVER DOHC Series Range Hood MAY NOT be installed on a Patio or Lanai a...

Страница 2: ...ation 6 Hood Dimensions 7 PART 2 Electrical Connection 8 PART 3 Determining Direction of Vent and Securing the Hood 9 Mounting Holes 9 Duct Cover 9 CARE CLEANING 10 Operating Controls 10 Removal of Fi...

Страница 3: ...lephone number listed in the warranty B Before servicing or cleaning unit switch power off at service panel and lock service panel and lock the service disconnection means to prevent power from being...

Страница 4: ...sher and you already know how to operate it 2 The fire is small and contained in the area where it started 3 The fire department is being called 4 You can fight the fire with your back to an exit RECO...

Страница 5: ...de authorities C When cutting or drilling into wall or ceiling do not damage electrical wiring and other hidden utilities D Some DANVER DOHC Series Range Hoods are for wall mounting only For safe and...

Страница 6: ...uct tape 7 Only use ductwork constructed of materials deemed acceptable by state municipal and local codes 8 Plan the installation so that all minimum clearances are met or exceeded Dimensions shown p...

Страница 7: ...rials should be installed with the combustible material structure a minimum of 36 above the cooking surface Hoods installed in custom canopies constructed of non combustible materials should be instal...

Страница 8: ...de ANSI NFPA 70 1990 or latest revision and local codes and ordinances A copy of this standard may be obtained from National Fire Protection Association 1 Batterymarch Park Quincy Massachusetts 02169...

Страница 9: ...ible Remove the filters Mark and drill screw holes through the hood as required Secure the hood by driving screws provided by others through the screw holes NOTE DRILLING THROUGH STAINLESS STEEL REQUI...

Страница 10: ...n filters and grease laden surfaces often to improve efficiency Proper cleaning is necessary to maintain performance and appearance while also ensuring safe operation The frequency of cleaning should...

Страница 11: ...ainless steel cleaner is used it is important to read the labels for chlorine compounds Chlorine is a corrosive substance If these compounds are present rinse thoroughly and dry with a soft lint free...

Страница 12: ...in the proper use and care of the product correct faulty installation change fuses or reset breakers Danver Inc disclaims and excludes any liability for implied warranties or for incidental or conseq...

Отзывы: