46
of 53
Performance data
Performance: Ambient/return = 35
°
°
°
°
C / 35
°
°
°
°
C
Cabinet data
Specification
Value
Unit
Description
Dimension
1245*460*405
mm
Height*Width*Depth(with flange)
Net weight
68
kg
Exclude the packing
Sheet metal mate-
rial
SUS +
ALMG
-
Out cover painted
Packing
1465*500*500
mm
Height*Width*Depth
Specification
Value
Unit
Description
Active cooling capacity
2000(50Hz)
2300(60Hz)
W
Include osmotic heat and solar
gain
Free cooling capacity
135
W
Include osmotic heat and solar
gain
(
Test Condition: Ambi-
ent/Return = 10
℃
/30
℃)
Refrigerant
1000
g
R134A
Internal airflow
755
M
3
/h
Active cooling mode
External airflow
860
M
3
/h
External fan running at H speed
Internal airflow
744
M
3
/h
Free cooling mode
Design pressure(HP)
3.1
MPa
-
Design pressure(LP)
1.0
Mpa
-
Operating pressure
101.3
KPa
Operating pressure
Disp. Pressure
100
Pa
Estimated pressure drop internal
Drop pressure
50
Pa
Pressure drop in climate unit (int.)
Operating
temperature
-40~+55
°
C
Operating temperature
66.5 without cabinet
dB(A)
66.1 with cabinet
dB(A)
Max. Noise Level (test method:
distance 1.5m, height 1.2m
referred GR487)
68.6 without cabinet
dB(A)
Noise
59.2 with cabinet
dB(A)
Max. Noise Level (test method:
According ISO 3744 )
Содержание DCU22-2000DH
Страница 51: ...51 of 53 12 Appendix Dimension...