11
of 53
4. Damper:
★
★
★
★
For Energy Saving Mode, the damper will open when these temperature conditions are met:
Return air temperature is above 18
℃
Supply air temperature is above 15
℃
Ambient air temperature must be 5
℃
lower than return air temperature. But when AC-mains is not
present or by compressor failure, the difference value is reduced to 2
℃
.
The damper will take 90 seconds to go from completely closed to completely open.
The damper will stop when these temperature conditions are met:
Supply air temperature is below 15
℃
and above 11
℃
The damper will be forced to close when these temperature conditions are met:
Supply air temperature is below 11
℃
Return air temperature is below 18
℃
★
★
★
★
For Emergency Cooling Mode, the damper will only open when AC mains failure or Compressor
failure.
In Emergency Cooling Mode, the damper will open when these temperature conditions are met:
Return air temperature is above 18
℃
Supply air temperature is above 15
℃
Ambient air temperature must be 2
℃
lower than return air temperature.
The damper will take 90 seconds to go from completely closed to completely open.
The damper will stop when these temperature conditions are met:
Supply air temperature is below 15
℃
and above 11
℃
The damper will be forced to close when these temperature conditions are met:
Supply air temperature is below 11
℃
Return air temperature is below 18
℃
Note: the Energy Saving Mode and Emergency Cooling Mode are the different soft-
ware version.