31
Operation
: Sub-menu: Alarm config. level
Sub-menu: Alarm config . level
Alarm configuration for the 10 hardware alarm outputs.
Any alarm that is configured to any of the 10 hardware alarm output, will also
be sent as SNMP alarm trap.
•
Each of the 10 hardware alarm outputs can be configured individually.
•
Alarm 1 and 2 output can take multiple alarms.
•
Alarm 3-10 can only handle single alarms/errors.
Alarm list
Default Alarm
output no .
Low voltage. (DC supply voltage low alarm )
5
High voltage. (DC supply voltage high alarm) 6
Temp. low. (Low temperature alarm.)
4
Temp. high 1. (High temperature 1 alarm)
9
Temp. high 2. (High temperature 2 alarm)
-
Temp. High 3. (High temperature 3 alarm)
-
Humidity low. (Low humidity alarm)
-
Humidity high. (High humidity alarm)
10
Filter flow 1 (Pressure level 1 alarm)
-
Filter flow 2 (Pressure level 2 alarm)
-
Fan 1. (Fan 1 alarm. Wrong RPM)
1
Fan 2. (Fan 2 alarm. Wrong RPM)
-
Onboard sensor (NTC fail)
-
Room sensor. (NTC fail )
7
Hotspot sensor. (NTC fail)
-
Ambient sensor 1 (Outdoor 1 sensor. NTC fail) 8
Ambient sensor 2 (Outdoor 2 sensor. NTC fail)
-
Digital 1. (Digital 1 input active) Fail Alarm
3
Digital 2. (Digital 2 input avtive)
-
Digital 3. (Digital 3 input active)
-
Filterguard 1. (Digital filterguard 1 alarm)
2
Filterguard 2. (Digital filterguard 2 alarm)
2
Network. (Network fail. Ethernet)
-
Memory. (Internal memory fail)
-
SD card. (SD card fail)
-
NO/NC. (alarm output normally open or normally closed)
Alarm Config
en