he relays operate on presence of a ground signal. There is no

latching capability. The relay contacts open when that

ground is removed. The individual LED should light on the front
panel as power is applied to each relay. This, however, does not
verify correct relay contact operation — only that ground is
applied to that individual relay coil.

TECHNICAL SPECIFICATIONS

DESCRIPTION

Input Voltage Range
Current Requirements

No relays Operating
One Relay Enabled
All Relays Enabled

Heat Dissipation

One Relay Enabled
All Relays Enabled

Current per Input to Operate
Resistance per Control Lead
Relay Contacts

Current Rating
Resistance

Operating Temperature
Physical Dimensions
Weight

DESCRIPTION

-21 to -56 VDC
@ -21VDC

@ -24 VDC

@ -48 VDC

@ -56 VDC

0.0 mA

0.0 mA

0.0 mA

0.0 mA

6.7 mA

7.0 mA

8.6 mA

9.0 mA

106.0 mA

112.0 mA

140.0 mA

148.0 mA

@ -21VDC

@ -24 VDC

@ -48 VDC

@ -56 VDC

0.48 Btu/Hr

0.58 Btu/Hr

1.41 Btu/Hr

1.72 Btu/Hr

7.68 Btu/Hr

9.28 Btu/Hr

22.56 Btu/Hr

27.52 Btu/Hr

6.0 mA
5.0K @ 24VDC; 1.5K @ 48VDC

1 Amp @ 30 VDC
0.1 Ohm
0° to 55° C.
1.4" x 6.0" x 5.6"
7.5 Ounces