46032-16-0199 <90-00149>
P
AGE
5
OPERATION
T
he relays operate on presence of a ground signal. There is no
latching capability. The relay contacts open when that
ground is removed. The individual LED should light on the front
panel as power is applied to each relay. This, however, does not
verify correct relay contact operation — only that ground is
applied to that individual relay coil.
TECHNICAL SPECIFICATIONS
DESCRIPTION
Input Voltage Range
Current Requirements
No relays Operating
One Relay Enabled
All Relays Enabled
Heat Dissipation
One Relay Enabled
All Relays Enabled
Current per Input to Operate
Resistance per Control Lead
Relay Contacts
Current Rating
Resistance
Operating Temperature
Physical Dimensions
Weight
DESCRIPTION
-21 to -56 VDC
@ -21VDC
@ -24 VDC
@ -48 VDC
@ -56 VDC
0.0 mA
0.0 mA
0.0 mA
0.0 mA
6.7 mA
7.0 mA
8.6 mA
9.0 mA
106.0 mA
112.0 mA
140.0 mA
148.0 mA
@ -21VDC
@ -24 VDC
@ -48 VDC
@ -56 VDC
0.48 Btu/Hr
0.58 Btu/Hr
1.41 Btu/Hr
1.72 Btu/Hr
7.68 Btu/Hr
9.28 Btu/Hr
22.56 Btu/Hr
27.52 Btu/Hr
6.0 mA
5.0K @ 24VDC; 1.5K @ 48VDC
1 Amp @ 30 VDC
0.1 Ohm
0° to 55° C.
1.4" x 6.0" x 5.6"
7.5 Ounces