6.3 Other
6.3.1
Safety valve
The purpose of the safety valve is to protect the substation from
excessive pressure.
The blow-off pipe from the safety valve must not be closed. The
blow-off pipe outlet should be placed so that it discharges freely
and it is possible to observe any dripping from the safety valve.
It is recommended to check the operation of safety valves at
intervals of 6 months. This is done by turning the valve head in
direction indicated.
6.3.2
Strainer
Strainers should be cleaned regularly by authorized personnel. The
frequency of cleaning would depend on operating conditions and
the manufacturer’s instructions.
6.3.3
GTU Pressure Equalizer
The GTU Pressure Equalizer absorbs the expansion on the
secondary side of the Termix water heaters and can be used as a
substitute to the safety valve.
Furthermore the pressure equalizer absorbs a possible increase in
pressure, so a discharge outlet is omitted.
The GTU Pressure Equalizer may not be applied in systems with hot
water circulation.