M-AI-VT-001-EN Rev.C.1
Controls Installation
Figure 49
Location of Bus Termination
Switch
The S801 switch on the drive module is used to
enable termination on the RS-485 port. Its default
setting is OFF. For every drive module, the S801
switch needs to be set to ON to communicate
with VTT compressor. The switch is located
behind the LCD cover, Figure 49.
Drive Module RS-485 Bus
Termination