Controls Installation
Table 27
Control Terminal Location
Table 28
Terminal Control Functions
Connector #
Description
1
Connector 1 provides four programmable digital input terminals, two additional terminals,
programmable as input or output, a 24VDC terminal supply voltage, and a common for optional
customer supplied 24V DC voltage.
2
Connector 2 provides terminals (+) 68 and (-) 69 are for an RS-485 serial communications connection.
3
Connector 3 provides two analog inputs, one analog input, 10VDC supply voltage, and commons
for the input and output. This feature is not utilized.
4
Connector 4 is a USB port available for use with the MCT 10 Set- up Software. This feature is not
utilized.
Terminal no
Function
12
24V DC power supply to digital inputs. The maximum output current is 200 mA.
19
Digital inputs for controlling the drive module. R=2 kΩ. Less than 5 V=logic 0 (open). Greater
than 10 V=logic 1 (closed). This is used for Interlock connection.
37
0-24V DC input for safety stop. Bridged. Shipped with jumper installed between 13 and 37.
61
RS-485 common.
68, 69
RS-485 interface and serial communication.
The control terminals provide for wiring input
signals to the following:
• Serial communication interface
Most control wiring is customer supplied unless
factory ordered. A 24V DC power supply is also
provided for use with the drive module control
inputs and outputs. Table 28 describes the
functions of the control terminals.
See Table 28 for terminal locations.
Figure 46
Control Card Terminals
12 13 18 19 27 29 32 33 20 37
61 68 69
39 42 50 53 54 55
3FNPWF KVNQFS UP FOBCMF 4BGF 4UPQ
Drive Module ModBus
and Interlock Connections
This section describes the ModBus and Interlock
connections between the CCM and the drive
module.
• Terminate Modbus on drive module side by
setting S801 to ON.
• Terminate Modbus on Compressor side
by putting jumper on JP2 located next to
connector J4.
• Always use STP cable for bus cabling.
• Follow all common installation practices.
• Low-impedance ground connection of the
shield is important.
• Connect a large surface of the shield to the
ground.