Refrigerant Piping Design
Figure 16
Motor Cooling Path
Figure 17
Motor Cooling Inlet Flange
Motor Cooling Port
Specifications
Economizer Port Types
The motor cooling inlet port is factory-fitted with
an electronic expansion valve. The compressor is
shipped with a liquid inlet tube to the expansion
valve with a 10 mm (3/8") inch sweat connection
and capped to hold the helium charge.
VTT compressors use two-stage centrifugal
compression with inter-stage port availability.
Two types of economizer arrangements can be
used; sub cooler (closed) or flash tank (open), see
Figures 21 and 22. Care must be taken to ensure
only refrigerant vapor enters the compressor.
To Evaporator
Electronnic Expansion Valve
Subcooled
Liquid
Superheated
Vapor
To the vapor side of the evaporator
Revision A
Revision B and later