![Danfoss VT2800 Series Скачать руководство пользователя страница 92](http://html1.mh-extra.com/html/danfoss/vt2800-series/vt2800-series_design-manual_507920092.webp)
VLT
®
2800 Series
-
overruled to stop with subsequent trip [5]
319 Analogue output terminal 42
(AO 42 FUNCTION)
Value:
No function (NO OPERATION)
[0]
External reference min.-max. 0-20 mA
(REF MIN-MAX = 0-20 MA)
[1]
External reference min.-max. 4-20 mA
(REF MIN-MAX = 4-20 MA)
[2]
Feedback min.-max. 0-20 mA
(FB MIN-MAX = 0-20 MA)
[3]
Feedback min.-max. 4-20 mA
(FB MIN-MAX = 4-20 MA)
[4]
Output frequency 0-max 0-20 mA
(0-FMAX = 0-20 MA)
[5]
Output frequency 0-max 4-20 mA
(0-FMAX = 4-20 MA)
[6]
✭
Output current 0-I
INV
0-20 mA
(0-IINV = 0-20 MA)
[7]
Output current 0-I
IINV
4-20 mA
(0-IINV = 4-20 MA)
[8]
Output power 0-P
M,N
0-20 mA
(0-PNOM = 0-20 MA)
[9]
Output power 0-P
M,N
4-20 mA
(0-PNOM = 4-20 MA)
[10]
Inverter temperature 20-100 °C 0-20 mA
(TEMP 20-100 C=0-20 MA)
[11]
Inverter temperature 20-100 °C 4-20 mA
(TEMP 20-100 C=4-20 MA)
[12]
Function:
The analogue output can be used for stating a
process value. It is possible to choose two types
of output signals 0 - 20 mA or 4 - 20 mA.
If used as a voltage output (0 - 10 V), a pull-down
resistor of 500
must be fitted to common
(terminal 55). If the output is used as a current
output the resulting resistance from the equipment
connected may not exceed 500
.
Description of choice:
No function
.
Is selected if the analogue
output is not to be used.
External Ref
MIN
- Ref
MAX
0-20 mA/4-20 mA.
An output signal is obtained, which is proportional
to the resulting reference value in the interval
Minimum reference, Ref
MIN
- Maximum reference,
Ref
MAX
(parameters 204/205).
FB
MIN
-FB
MAX
0-20 mA/ 4-20 mA.
An output signal is obtained, which is proportional to the
feedback value in the interval Minimum feedback, FB
MIN
- Maximum feedback, FB
MAX
(parameter 414/415).
0-f
MAX
0-20 mA/4-20 mA.
An output signal is obtained, which is proportional to
the output frequency in the interval 0 - f
MAX
(parameter
202
Output frequency, high limit, f
MAX
).
0 - I
INV
0-20 mA/4-20 mA.
An output signal is obtained, which is proportional
to the output current in the interval 0 - I
INV
0 - P
M,N
0-20 mA/4-20 mA.
An output signal is obtained, which is proportional to
the present output power. 20 mA corresponds to the
value set in parameter 102
Motor power, P
M,N
.
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.E9.02 - VLT is a registered Danfoss trademark
92