VLT
®
2800 Series
Programming
LCP 2 control panel. First all parameter values are
copied to the LCP 2 control panel, which can then
be moved to another frequency converter. Here all
parameter values can be copied from the LCP 2
control unit to the frequency converter.
■
Setup shift
-
Selection of Setup via terminals 29 and 33.
Par. 305
Digital input
=
Selection of Setup, lsb
[31]
Par. 307
Digital input
=
Selection of Setup, msb
[32]
Par. 004
Active setup
=
Multi Setup
[5]
004 Active Setup
(ACTIVE SETUP)
Value:
Factory Setup (FACTORY SETUP)
[0]
✭
Setup 1 (SETUP 1)
[1]
Setup 2 (SETUP 2)
[2]
Setup 3 (SETUP 3)
[3]
Setup 4 (SETUP 4)
[4]
Multi Setup (MULTI SETUP)
[5]
Function:
The active parameter Setup is selected here. All
parameters can be programmed in four individual
parameter Setups. Shifts between Setups can
be made in this parameter via a digital input
or via serial communication.
Description of choice:
Factory Setup
[0] contains the factory-set parameter
values.
Setup 1-4
[1]-[4] are four individual
Setups which can be selected as required.
Multi
Setup
[5] is used where remote-controlled shifts
between the four Setups via a digital input or via
serial communication is required.
005 Programming Setup
(EDIT SETUP)
Value:
Factory Setup (FACTORY SETUP)
[0]
Setup 1 (SETUP 1)
[1]
Setup 2 (SETUP 2)
[2]
Setup 3 (SETUP 3)
[3]
Setup 4 (SETUP 4)
[4]
✭
Active Setup (ACTIVE SETUP)
[5]
Function:
You can select which Setup you want to programme
during operation (applies both via the control
panel and the serial communication port). It is,
for example, possible to programme
Setup 2
[2], while the active Setup is set to
Setup 1
[1]
in parameter 004
Active Setup
.
Description of choice:
Factory Setup
[0] contains the factory-set data
and can be used as a source of data if the
other Setups are to be reset to a known status.
Setup 1-4
[1]-[4] are individual Setups that can
be programmed freely during operation. If
Active
Setup
[5] is selected, the programming Setup will
be equal to parameter 004
Active Setup
.
NB!:
If data is modified or copied to the active
Setup, the modifications have an immediate
effect on the unit
’
s operation.
006 Setup copying
(SETUP COPY)
Value:
✭
No copying (NO COPY)
[0]
Copy to Setup 1 from #
(COPY TO SETUP 1)
[1]
Copy to Setup 2 from #
(COPY TO SETUP 2)
[2]
Copy to Setup 3 from #
(COPY TO SETUP 3)
[3]
Copy to Setup 4 from #
(COPY TO SETUP 4)
[4]
Copy to all Setups from # (COPY TO ALL)
[5]
Function:
You can copy from the selected active Setup in
parameter 005
Programming setup
to the selected
Setup or Setups in this parameter.
NB!:
Copying is only possible in Stop (motor stopped
in connection with a stop command).
Description of choice:
Copying begins when the required copying function
has been selected and the [OK]/[CHANGE DATA]
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.E9.02 - VLT is a registered Danfoss trademark
61