Programmable SyncPos motion controller
69
SYNCMWINS
The Marker Window Slave SYNCMWINS shows
how large the permitted tolerance for the occur-
rence of the markers is.
With the works setting „0“ the window is not moni-
tored, which means that it is always synchronized
to the next marker even if this has a considerably
larger interval.
At every other setting only those markers are ac-
cepted which are within the window. If there is no
marker within the tolerance window the correspon-
ding flag (SYNCSTAT) is set and no marker correc-
tion takes place. The corresponding other marker
is also ignored and only corrected the next time –
i.e. no catching up to the next marker.
When SYNCM (or SYNCCSTART) is started the
monitoring only begins when the first marker has
been found.
Content
Tolerance window for slave marker monitoring
Parameter Group
Axis parameter Synchronization AXS
CAM-Editor: index card Synchron.
Unit
q c
or in CAM mode: UU
Value range
0 … MLONG or. max. Marker interval
SYNCMPULSS (59)
★
0
0 =
The window is not monitored.
1 … MLONG =
Only one marker is accepted
within the window. If no marker
is within the tolerance window,
the corresponding flag
(SYNCSTAT) is set and no
marker correction carried out.
This flag can be reset with an
interrupt (ON STATBIT).
NB!
Changes of the parameter will become active
immediately – not only after the next SYNCM
command.
70
ESCCOND
With ESCCOND you can determine how the VLT
will react to a program termination using ESC.
Content
Condition on program termination
Parameter Group
Axis parameters Inputs/Outputs AXI
CAM-Editor: index card Inp/Outp
Value range
0 … 2
★
0
0 =
The motor is stopped with maximum
deceleration, the brake is activated (if defined),
the master simulation is stopped.
The outputs remain in the current status.
1 =
As 0, but all outputs including the VLT5000
outputs 11, 14, 42 and 45 (resp. the
VLT5000Flux outputs 26 and 46) are set at
“0”.
Exception
: The brake output – if defined –
is always activated.
2 =
As “0”, but all outputs including the VLT5000
outputs 11, 14, 42 and 45 (resp. the
VLT5000Flux outputs 26 and 46) are set at
“1”.
Exception
: The brake output – if defined –
is always activated
Parameter Reference