199
MG.10.J8.02 – VLT is a registered Danfoss trade mark
Programmable SyncPos motion controller
Unit
τ
_filt (
µ
sec)
Value range
–M LONG … M LONG
★
0
-999 … 999 = Standard table
Standard table
Encoder resolution
t_filt (msec)
250
39500
256
38600
500
19500
512
19000
1000
9500
1024
9300
2000
4500
2048
4400
2500
3500
4096
1900
5000
1400
66
SYNCVELREL
This parameter indicates by how many percent the
slave drive can deviate from the velocity of the
master while attempting re-synchronization. For
example, during changes in SYNCPOSOFFS (54) or
at the start of synchronization or during the correc-
tion of deviation for marker evaluation. The follo-
wing is valid:
If the slave need to catch up it runs with the maxi-
mum speed allowed; this is either the speed set with
VEL or the master velocity calculated with
MAVEL + MAVEL * SYNCVELREL/100
depending which of the two is less. (MAVEL is the
actual master velocity).
If the slave needs to slow down and wait for the
master it will run with at least the following speed
MAVEL – MAVE L * SYNCVELR EL/100.
That means, if SYNCVELREL is 50, for example,
the slave will not run slower than MAVEL/2.
Content
tolerated deviance of the slave drive from the master
velocity in %
Syntax
set syncvelrel value
value = percent value
Parameter Group
Axis parameter Synchronization AXS
CAM-Editor: index card Synchron.
Unit
%
Value range
0 … MLONG
★
0
0 = OFF, i.e. no restriction
Parameter Reference