6.4 EtherCAT® ID Assignment
EtherCAT
®
needs no special ID assignment (IP address). Special ID assignment is only required when using indirect communication via
the VLT
®
Servo Toolbox software.
6.5 Ethernet POWERLINK® ID Assignment
6.5.1 Overview
Ethernet POWERLINK
®
master communication must not be active when using the VLT
®
Servo Toolbox to assign IDs to the devices. ID
assignment via the VLT
®
Servo Toolbox is only possible when acyclic Ethernet POWERLINK
®
communication is used. If Ethernet
POWERLINK
®
cyclic communication is already started, perform a power cycle to stop it.
Detach the PLC and carry out a power cycle before setting IDs. Alternatively, in the POWERLINK
®
interface, restart the PLC in
Service
Mode
while parameter
Basic Ethernet in Service Mode
is set to
Basic Ethernet enabled
.
6.5.2 Single Device ID Assignment
When assigning an ID to a single device, use the
Device Information
window in the VLT
®
Servo Toolbox (see the VLT
®
Servo Drive
System ISD 510, DSD 510, MSD 510 Programming Guide for further information).
Setting an ID to a device can also be done via the LCP.
6.5.2.1 Setting the Node ID Directly on a Servo Drive or on the System Modules
Context:
All IP-related parameters are located in parameter group
12-0* IP Settings
. According to the Ethernet POWERLINK
®
standard, the IP
address is fixed to 192.168.100.xxx. The last number is the value in parameter
12-60 Node ID
. For parameter
12-02 Subnet Mask
, the IP
address is fixed to 255.255.255.0 and cannot be changed.
Procedure
1. Attach the LCP to the servo drive or system module for which the
Node ID
should be changed.
2. Press the
Hand On
button for >1 s to make the LCP the controlling interface.
3. Press the
Main Menu
button then scroll down to submenu
12-** Ethernet
and press
OK
.
4. Scroll down to submenu
12-6* Ethernet POWERLINK
and press
OK
.
5. Change the PSM 510/DAM 510 node ID to the desired value (1–239).
6. Press
OK
to confirm the selection then wait for the ID assignment procedure to complete.
7. Carry out a power cycle to ensure that all ID changes are in effect and operational on the fieldbus.
6.5.2.2 Setting the Node ID for a Single Servo Drive via the Power Supply Module (PSM 510) or
Decentral Access Module (DAM 510) via the LCP
Context:
It is also possible to change the
Node ID
of a servo drive when the LCP is connected to the PSM 510 or DAM 510. This functionality is
contained in parameter group
54-** ID Assignment
in subgroup
54-1* Manual
.
Commissioning
Operating Guide | VLT® Multiaxis Servo Drive MSD 510 System
AQ262450196490en-000101 / 175R1170
82 | Danfoss A/S © 2019.10