Procedure
1. Connect the Ethernet cable from the PLC to the Ethernet input connector [1].
2. Connect the Ethernet cable from the Ethernet output connector [2] to the next module.
3. Insert the wires into the 24/48 V IN connector.
4. Insert the 24/48 V IN connector [3].
5. Insert the wires into the STO connector IN connector.
6. Insert the STO connector IN (STO PSM) connector [4].
7. Insert the wires into the STO connector OUT connector.
8. Insert the STO connector OUT (STO PSM) connector [5].
9. If I/Os are required, insert the wires into the I/O connector and insert the connector (I/O PSM) [6].
10. If a relay is required, insert the wires into the relay connector and insert the connector (REL PSM) [7].
5.9.2.2 Connecting the Cables on the Bottom of the Power Supply Module PSM 510
Context:
2
1
3
4
e3
0b
g4
66
.1
0
1 Holder for internal brake resistor connector when not in use
3 PE screws
2 AC mains supply connector
4 Internal/external brake resistor connector
Illustration 51: Connectors on the Bottom of PSM 510
Procedure
1. Insert the wires into the AC mains supply connector.
2. Insert the AC mains supply connector [2].
3. If an external brake resistor is required:
A Unplug the internal brake resistor connector [4] and insert the external brake connector in its place.
B Plug the internal brake resistor connector to the internal brake connector holder [1].
4. Connect the PSM 510 to the PE screw on the front side [3] using a PE wire. The tightening torque is 3 Nm.
Electrical Installation
Operating Guide | VLT® Multiaxis Servo Drive MSD 510 System
AQ262450196490en-000101 / 175R1170
72 | Danfoss A/S © 2019.10