Table 140: Pin Assignment of AC Mains Connector
Pins
(left to
right)
Descrip‐
tion
Notes
Rating/parameter
1
L3
Used to connect
L1/L2/L3
Nominal voltage: 400–480 V AC ±10%
Nominal power: 30 kW
Maximum cross-section: 16 mm
2
(AWG 4)
Conductor cross-section range 0.75–16 mm
2
, solid or flexible (AWG 18–AWG 4)
2
L2
3
L1
11.7.7.1 Mains Cable Cross-Sections for PSM 510
Table 141: Mains Cable Cross-Sections for PSM 510
PSM 510 (10 kW)
PSM 510 (20 kW)
PSM 510 (30 kW)
Minimum cable cross-section for CE
4 mm
2
(minimum 70 °C, Cu)
16 mm
2
(minimum 70 °C, Cu)
16 mm
2
(minimum 90 °C, Cu)
Minimum cable cross-section for UL
AWG 10
(minimum 60 °C, Cu)
AWG 6
(minimum 60 °C, Cu)
AWG 4
(minimum 75 °C, Cu)
11.7.8 Motor Connector
The motor connectors are located on the bottom of the Servo Drive Modules (SDM 511 and SDM 512).
e
3
0
b
g
4
5
2
.1
0
Illustration 140: Motor Connector
Specifications
Operating Guide | VLT® Multiaxis Servo Drive MSD 510 System
AQ262450196490en-000101 / 175R1170
224 | Danfoss A/S © 2019.10
Содержание VLT MSD 510
Страница 1: ...Operating Guide VLT Multiaxis Servo Drive MSD 510 System...
Страница 2: ......