Possible Causes
•
Faulty brake resistor.
•
Internal/external brake resistor not connected.
Troubleshooting
•
Remove the power to the device, wait for the discharge time to elapse, then replace the brake resistor.
9.2.2.14 Brake Chopper Error
This fault applies to the PSM 510.
Possible Causes
•
Faulty brake chopper.
•
Brake chopper power exceeds the power cycle limit.
•
Incorrect parameterization.
Troubleshooting
•
Check the parameterization of the brake chopper.
•
Check the brake chopper connection.
•
Measure the resistance of the brake chopper and compare it with the parameter settings.
9.2.2.15 Internal Fan Error
This fault applies to PSM 510 and SDM 511/SDM 512.
Possible Causes
•
Fan is not mounted.
•
Fan is blocked.
Troubleshooting
•
Check if the fan is blocked.
•
Check the fan cables for proper connection or damage.
9.3 Error Codes
9.3.1 No error (0x0000 / 0x0)
This error code is valid for PSM 510, DAM 510, ACM 510, and SDM 511/SDM 512.
Table 36: No error (0x0000 / 0x0)
Code
PROFINET
®
code
Name
Severity (warning/error/trip lock)
Description
LCP name
0x0000
0x0
No error
Error
No error.
-
Diagnostics
Operating Guide | VLT® Multiaxis Servo Drive MSD 510 System
AQ262450196490en-000101 / 175R1170| 171
Danfoss A/S © 2019.10