4 Parameter Descriptions
4.1 Parameters: 0-** Operation and Display
0-01 Language
Select the language to be used in the display.
Option:
Function:
[0]
*
English
[1]
Deutsch
[2]
Francais
[3]
Dansk
[4]
Spanish
[5]
Italiano
0-03 Regional Settings
Option:
Function:
NOTICE
This parameter cannot be adjusted while
the motor is running.
[0]
*
Interna-
tional
Activates
parameter 1-20 Motor Power [kW]
for
setting the motor power in kW and sets the
default value of
parameter 1-23 Motor Frequency
to 50 Hz.
[1]
US
Activates
parameter 1-20 Motor Power [kW]
for
setting the motor power in hp and sets the
default value of
parameter 1-23 Motor Frequency
to 60 Hz.
0-04 Operating State at Power-up (Hand)
Option:
Function:
Selects the operating mode upon
reconnection of the frequency converter to
mains voltage after power down in hand on
mode.
[0]
Resume
Restarts the frequency converter, maintaining
the start/stop settings (applied by [Hand On/
Off]) selected before the power-down of the
frequency converter.
[1]
*
Forced stop,
ref=old
Restarts the frequency converter with a saved
local reference after mains voltage reappears
and after pressing [Hand On].
[2]
Forced stop,
ref=0
Resets the local reference to 0 upon
restarting the frequency converter.
0-06 GridType
Select the supply voltage, frequency, and type.
Option:
Function:
[10]
380-440V/50Hz/IT-grid
[11]
380-440V/50Hz/Delta
[12]
380-440V/50Hz
[20]
440-480V/50Hz/IT-grid
0-06 GridType
Select the supply voltage, frequency, and type.
Option:
Function:
[21]
440-480V/50Hz/Delta
[22]
440-480V/50Hz
[100]
200-240V/60Hz/IT-grid
[101]
200-240V/60Hz/Delta
[102]
200-240V/60Hz
[110]
380-440V/60Hz/IT-grid
[111]
380-440V/60Hz/Delta
[112]
380-440V/60Hz
[120]
440-480V/60Hz/IT-grid
[121]
440-480V/60Hz/Delta
[122]
440-480V/60Hz
0-07 Auto DC Braking
Option: Function:
Protective function against overvoltage at coast in IT
grid environment. This parameter is active only when
[1] On
is selected in this parameter, and IT-grid options
are selected in
parameter 0-06 GridType
.
[0]
Off This function is not active.
[1]
*
On This function is active.
0-10 Active Set-up
Select the set-up to control the frequency converter functions.
Program parameters in set-ups 1–4. Use the factory set-up to
return the initial state. Use multi set-up for remote control.
Option:
Function:
[1]
*
Set-up 1
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
[9]
Multi Set-up
0-11 Programming Set-up
Select the set-up to be programmed during operation; either the
active set-up or the inactive set-up. The set-up number being
edited flashes in the LCP.
Option:
Function:
[1]
Set-up 1
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
[9]
*
Active Set-up
Parameter Descriptions
Programming Guide
MG07C102
Danfoss A/S © 12/2015 All rights reserved.
23
4