Frequency converter
typical shaft output [kW (hp)]
P4K0
4
(5.5)
P5K5
5.5
(7.5)
P7K5
7.5
(10)
P11K
11
(15)
P15K
15
(20)
P18K
18.5
(25)
P22K
22
(30)
Enclosure protection rating IP20 (IP21/Type 1 as
option)
K2
K2
K3
K4
K4
K5
K5
Output current
Shaft output
4
5.5
7.5
11
15
18.5
22
Continuous (3x380–440 V) [A]
9
12
15.5
23
31
37
42.5
Continuous (3x441–480 V) [A]
8.2
11
14
21
27
34
40
Intermittent (60 s overload) [A]
14.4
19.2
24.8
34.5
46.5
55.5
63.8
Continuous kVA (400 V AC) [kVA]
6.2
8.3
10.7
15.9
21.5
25.6
29.5
Continuous kVA (480 V AC) [kVA]
6.8
9.1
11.6
17.5
22.4
28.3
33.3
Maximum input current
Continuous (3x380–440 V) [A]
8.3
11.2
15.1
22.1
29.9
35.2
41.5
Continuous (3x441–480 V) [A]
6.8
9.4
12.6
18.4
24.7
29.3
34.6
Intermittent (60 s overload) [A]
13.3
17.9
24.2
33.2
44.9
52.8
62.3
More specifications
Maximum cable cross-section (mains, motor,
brake, and load sharing) [mm
2
(AWG)]
4 (12)
16 (6)
Estimated power loss at rated maximum load
[W]
1)
115.5
157.5
192.8
289.5
393.4
402.8
467.5
Weight enclosure protection rating IP20 [kg (lb)]
3.6 (7.9)
3.6 (7.9)
4.1 (9.0)
9.4 (20.7)
9.5 (20.9)
12.3 (27.1)
12.5 (27.6)
Weight enclosure protection rating IP21 [kg (lb)] 5.5 (12.1)
5.5 (12.1)
6.5 (14.3) 10.5 (23.1)
10.5 (23.1)
14.0 (30.9)
14.0 (30.9)
Efficiency [%]
2)
98.0
97.8
97.7
98.0
98.1
98.0
98.0
Table 9.2 Mains Supply 3x380–480 V AC
Frequency converter
typical shaft output [kW (hp)]
PK37
0.37
(0.5)
PK55
0.55
(0.75)
PK75
0.75
(1.0)
P1K1
1.1
(1.5)
P1K5
1.5
(2.0)
P2K2
2.2
(3.0)
P3K7
3.7
(5.0)
Enclosure protection rating IP20 (IP21/Type 1 as
option)
K1
K1
K1
K1
K1
K2
K3
Output current
Continuous (3x200–240 V) [A]
2.2
3.2
4.2
6
6.8
9.6
15.2
Intermittent (60 s overload) [A]
3.5
5.1
6.7
9.6
10.9
15.4
24.3
Continuous kVA (230 V AC) [kVA]
0.9
1.3
1.7
2.4
2.7
3.8
6.1
Maximum input current
Continuous (3x200–240 V) [A]
1.8
2.7
3.4
4.7
6.3
8.8
14.3
Intermittent (60 s overload) [A]
2.9
4.3
5.4
7.5
10.1
14.1
22.9
More specifications
Maximum cable cross-section (mains, motor,
brake, and load sharing) [mm
2
(AWG)]
4 (12)
Estimated power loss at rated maximum load
[W]
1)
29.4
38.5
51.1
60.7
76.1
96.1
147.5
Weight enclosure protection rating IP20 [kg
(lb)]
2.3 (5.1)
2.3 (5.1)
2.3 (5.1)
2.3 (5.1)
2.3 (5.1)
2.5 (5.5)
3.6 (7.9)
Weight enclosure protection rating IP21 [kg
(lb)]
4.0 (8.8)
4.0 (8.8)
4.0 (8.8)
4.0 (8.8)
4.0 (8.8)
5.5 (12.1)
6.5 (14.3)
Efficiency [%]
2)
96.4
96.6
96.3
96.6
96.5
96.7
96.7
Table 9.3 Mains Supply 3x200–240 V AC
Specifications
VLT
®
Midi Drive FC 280
54
Danfoss A/S © 10/2017 All rights reserved.
MG07A402
9
9
Содержание VLT Midi Drive FC 280
Страница 1: ...ENGINEERING TOMORROW Operating Guide VLT Midi Drive FC 280 vlt drives danfoss com ...
Страница 2: ......