7 Application Examples
7.1 Introduction
The examples in this section are intended as a quick
reference for common applications.
•
Parameter settings are the regional default values
unless otherwise indicated (selected in
parameter 0-03 Regional Settings
).
•
Parameters associated with the terminals and
their settings are shown next to the drawings.
•
Required switch settings for analog terminals 53
or 54 are also shown.
NOTICE
When the STO feature is not used, a jumper wire is
required between terminals 12, 37, and 38 for the
frequency converter to operate with factory default
programming values.
7.2 Application Examples
7.2.1 AMA
Parameters
130BF096.10
FC
+24 V
D IN
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
12
13
18
19
27
29
32
33
50
53
54
55
42
A OUT
D IN
+24 V
Function
Setting
Parameter 1-29 A
utomatic Motor
Adaptation
(AMA)
[1] Enable
complete
AMA
Parameter 5-12 T
erminal 27
Digital Input
*[2] Coast
inverse
* = Default value
Notes/comments:
Set
parameter group 1-2* Motor
Data
according to motor
specifications.
NOTICE
If terminal 13 and 27 are
not connected, set
parameter 5-12 Terminal 27
Digital Input
to
[0] No
operation
.
Table 7.1 AMA with T27 Connected
7.2.2 Speed
Parameters
130BE204.11
+24 V
D IN
D IN
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
12
13
18
19
27
29
32
33
50
53
54
55
42
0 ~10 V
+
-
FC
+24 V
Function
Setting
Parameter 6-10 T
erminal 53 Low
Voltage
0.07 V*
Parameter 6-11 T
erminal 53 High
Voltage
10 V*
Parameter 6-14 T
erminal 53 Low
Ref./Feedb. Value
0
Parameter 6-15 T
erminal 53 High
Ref./Feedb. Value
50
Parameter 6-19 T
erminal 53 mode
[1] Voltage
* = Default value
Notes/comments:
Table 7.2 Analog Speed Reference (Voltage)
Parameters
130BF097.10
+24 V
D IN
D IN
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
12
13
18
19
27
29
32
33
50
53
54
55
42
4 - 20mA
+
-
FC
+24 V
Function
Setting
Parameter 6-22 T
erminal 54 Low
Current
4 mA*
Parameter 6-23 T
erminal 54 High
Current
20 mA*
Parameter 6-24 T
erminal 54 Low
Ref./Feedb. Value
0
Parameter 6-25 T
erminal 54 High
Ref./Feedb. Value
50
Parameter 6-29 T
erminal 54 mode
[0] Current
* = Default value
Notes/comments:
Table 7.3 Analog Speed Reference (Current)
Application Examples
VLT
®
Midi Drive FC 280
42
Danfoss A/S © 10/2017 All rights reserved.