3.4 Current Ratings (IEC Ratings)
N O T I C E
Contact the local supplier for ratings under operating conditions not covered by these rating charts.
e7
7h
a8
20
.1
0
Sta
rter
cu
rren
t ra
ting
Sta
rt c
urre
nt (m
ultip
le o
f FL
C)
Sta
rt tim
e (s
eco
nds
)
Off
tim
e (s
eco
nds
)
80 A
: AC-53b
3.5 - 15
:
345
Illustration 2: AC53b Format (Bypassed Current Rating)
e7
7h
a8
21
.1
0
Sta
rter
cu
rren
t ra
ting
Sta
rt c
urre
nt (m
ultip
le o
f FL
C)
Sta
rt tim
e (s
eco
nds
)
On
-loa
d d
uty
cyc
le (%
)
351 A
: AC-53a
3.5 - 15
:
50
6
Sta
rts p
er h
our
-
Illustration 3: AC53a Format (Non-bypassed Current Rating)
N O T I C E
All ratings are calculated at an altitude of 1000 m (3280 ft) and an ambient temperature of 40 °C (104 °F).
Table 2: In-line Installation, Internal Bypassed, MCD6-0020B ~ MCD6-0042B
3.0-10:350
3.5-15:345
4.0-10:350
4.0-20:340
5.0-5:355
MCD6-0020B
24
20
19
16
16
MCD6-0034B
42
34
34
27
31
MCD6-0042B
52
42
39
34
34
Table 3: In-line Installation, Internal Bypassed, MCD6-0063B ~ MCD6-1250B
3.0-10:590
3.5-15:585
4.0-10:590
4.0-20:580
5.0-5:595
MCD6-0063B
64
62
60
50
53
MCD6-0069B
69
69
69
62
64
MCD6-0086B
105
86
84
68
76
MCD6-0108B
115
107
104
86
95
MCD6-0129B
135
129
126
103
115
MCD6-0144B
184
143
139
115
127
MCD6-0171B
200
170
165
138
150
MCD6-0194B
229
194
187
157
170
AQ262141844215en-000401 / 175R1174
14 | Danfoss A/S © 2020.12
System Design
VLT® Soft Starter MCD 600
Operating Guide