Table 201: 12-21 - Location ID
Range
Function
*0
0–65535
Sets the soft starter's unique location ID.
10.17 Parameter Group 20-** Advanced
Table 202: 20-1 - Tracking Gain
Range
Function
*50%
1–200%
Fine-tunes the behavior of the adaptive control algorithm.
Table 203: 20-2 - Pedestal Detect
Range
Function
* 80%
0–200%
Adjusts the behavior of the adaptive control algorithm for soft stop.
Table 204: 20-3 - Bypass Contactor Delay
Range
Function
*100 ms 50–200 ms Sets the soft starter to match the bypass contactor closing/opening time. Set according to the specifica-
tions of the bypass contactor used. If this time is too short, the soft starter will trip.
Table 205: 20-4 - Model Rating
Range
Function
*Model
de-
pend-
ent
Model
de-
pend-
ent
The soft starter’s internal model reference, as shown on the silver label on the side of the unit. This parameter
is a read-only parameter. If the software is to be upgraded (SW version 3.0 and after), as part of applying the
upgrade firmware update, the MCD 600 requests the M/R code to be entered. This code is printed on the
product serial label as shown [1] below. This is only required to be entered once as part of the update proc-
ess. When entered, the parameter switches back to read-only If a wrong value by mistake has been entered,
this can re-activate the field by pressing [
▵
]/[
▿
] and cycling the control power. Once the code is re-entered, it
will again become read-only.
M/R: 0085
Made in New Zealand
RoHS
e
7
7
h
a
7
2
5
.1
0
1
N O T I C E
This parameter can only be adjusted by authorized servicing agents.
Table 206: 20-5 - Screen Timeout
Option
Function
Sets the timeout for the menu to close automatically if no LCP activity is detected.
*
1 minute
2 minutes
AQ262141844215en-000401 / 175R1174
114 | Danfoss A/S © 2020.12
Programmable Parameters
VLT® Soft Starter MCD 600
Operating Guide
Содержание VLT MCD 600
Страница 1: ...Operating Guide VLT Soft Starter MCD 600 vlt drives danfoss com...
Страница 2: ......
Страница 3: ......
Страница 4: ......
Страница 5: ......
Страница 6: ......
Страница 139: ...AQ262141844215en 000401 175R1174 135 Danfoss A S 2020 12 Index VLT Soft Starter MCD 600 Operating Guide...