3.1.4 Topology
The MCA 121 features a build-in Ethernet-switch, thus having two Ethernet RJ-45 connectors. This enables the possibility for
connecting several EtherNet/IP options in a line topology as an alternative to the typical star-topology.
The two ports are equal, in the sense that they are transparent for the option. If only one connector is used, either port can
be used.
AutomationDrive
VLT
AutomationDrive
VLT
AutomationDrive
VLT
AutomationDrive
VLT
AutomationDrive
VLT
AutomationDrive
VLT
AutomationDrive
VLT
AutomationDrive
VLT
130BA903.10
Illustration 3.2 Star topology
AutomationDrive
VLT
AutomationDrive
VLT
AutomationDrive
VLT
AutomationDrive
VLT
AutomationDrive
VLT
AutomationDrive
VLT
AutomationDrive
VLT
130BA904.10
Illustration 3.3 Line topology
NOTE
For line topology please refer to section: “Recommended design rules” In a line topology all frequency converters must be
powered, either by mains or by their 24 V DC option cards, for the build-in switch to work.
NOTE
Please observe that mounting frequency converters of different power-sizes in a line topology may result in unwanted
power-off behaviour.
Smaller frequency converters discharge faster than bigger ones. This can result in loss of link in the line topology, which
may lead to control word timeout.
To avoid this, mount the frequency converters with the longest discharge time first in the line topology.
How to Install
MCA 121 EtherNet/IP
8
MG.90.J3.02 - VLT
®
is a registered Danfoss trademark
3
3
Содержание VLT MCA 121 EtherNet/IP
Страница 1: ...MAKING MODERN LIVING POSSIBLE Operating Instructions MCA 121 EtherNet IP...
Страница 58: ...www danfoss com drives MG90J302 130R0430 MG90J302 Rev 2011 03 29...
Страница 59: ......