12.3 Emergency Codes
Code
Severity
Description
0x3100
Error
Input voltage (U
DC
) above absolute maximum.
0x3101
Error
Input voltage (U
DC
) below absolute minimum.
0x3102
Error
Input voltage (U
DC
) below intermediate voltage (U
ZK
) during power-up.
0x3110
Error
24 V power supply loss.
0x3111
Error
24 V power supply timeout during initialisation.
0x3118
Error
5 V CAN power supply loss.
0x3119
Error
5 V CAN power supply timeout during initialisation.
0x3180
Warning
Switch on, nominal U
DC
range: Input voltage above maximum.
0x3181
Warning
Switch on, nominal U
DC
range: Input voltage below minimum.
0x3190
Warning
Switch on: 24 V power supply bad.
0x3191
Warning
Switch on: 5 V CAN power supply bad.
0x3200
Error
Hazardous intermediate circuitry voltage.
0x3201
Error
Intermediate circuitry voltage (U
ZK
) drop during operation.
0x3280
Warning
Intermediate circuitry voltage (U
ZK
) over voltage during operation.
0x4280
Warning
Switch on: Heat sink temperature above maximum.
0x5030
Error
Fuse 1 blown.
0x5031
Error
Fuse 2 blown.
0xFF01
Error
Power-up timeout.
0xFF02
Error
Power-down timeout.
0xFF90
Warning
Switch on: No safety power.
0xFF91
Warning
Safety power 1 loss.
0xFF92
Warning
Safety power 2 loss.
Table 12.1 Emergency Codes
Appendix
VLT
®
ISD Connection Box Operating Instructions
MG75G102 - VLT
®
is a registered Danfoss trademark
51
12
12
Содержание VLT ISD Connection Box
Страница 1: ...MAKING MODERN LIVING POSSIBLE Operating Instructions VLT ISD Connection Box...
Страница 2: ......
Страница 57: ...Index VLT ISD Connection Box Operating Instructions MG75G102 VLT is a registered Danfoss trademark 55...
Страница 58: ...www danfoss com drives MG75G102 175R1124 MG75G102 Rev 2012 10 29...