7.3.2.1 Recommended Fuses for CE Compliance
Drive
modules
in
system
FC 302
modules
[kW]
FC 102
and FC
202
modules
[kW]
Recommended
fuse
Recommended
fuse
(maximum)
2
N250
N315
aR-630
aR-630
2
N315
N355
aR-630
aR-630
2
N355
N400
aR-630
aR-630
2
N400
N450
aR-800
aR-800
2
N450
N500
aR-800
aR-800
4
N500
N560
aR-900
aR-900
4
N560
N630
aR-900
aR-900
4
N630
N710
aR-1600
aR-1600
4
N710
N800
aR-1600
aR-1600
4
N800
N1M0
aR-1600
aR-1600
Table 7.16 12-Pulse Drive Systems (380–500 V AC)
Drive
modules
in
system
FC 302
modules
[kW]
FC 102
and FC
202
modules
[kW]
Recommended
fuse
Recommended
fuse
(maximum)
2
N450
N500
aR-1600
aR-1600
4
N500
N560
aR-2500
aR-2500
4
N560
N630
aR-2500
aR-2500
4
N630
N710
aR-2500
aR-2500
4
N710
N800
aR-2500
aR-2500
4
N800
N1M0
aR-2500
aR-2500
Table 7.17 6-Pulse Drive Systems (380–500 V AC)
Drive
modules
in
system
FC 302
modules
[kW]
FC 102
and FC
202
modules
[kW]
Recommended
fuse
Recommended
fuse
(maximum)
2
N250
N315
aR-550
aR-550
2
N315
N355
aR-630
aR-630
2
N355
N400
aR-630
aR-630
2
N400
N500
aR-630
aR-630
2
N500
N560
aR-630
aR-630
2
N560
N630
aR-900
aR-900
4
N630
N710
aR-900
aR-900
4
N710
N800
aR-900
aR-900
4
N800
N900
aR-900
aR-900
4
N900
N1M0
aR-1600
aR-1600
4
N1M0
N1M2
aR-1600
aR-1600
Table 7.18 12-Pulse Drive Systems (525–690 V AC)
Drive
modules
in
system
FC 302
modules
[kW]
FC 102
and FC
202
modules
[kW]
Recommended
fuse
Recommended
fuse
(maximum)
4
N630
N710
aR-1600
aR-1600
4
N710
N800
aR-2000
aR-2000
4
N800
N900
aR-2500
aR-2500
4
N900
N1M0
aR-2500
aR-2500
4
N1M0
N1M2
aR-2500
aR-2500
Table 7.19 6-Pulse Drive Systems (525–690 V AC)
Specifications
User Guide
MG37L202
Danfoss A/S © 08/2017 All rights reserved.
69
7
7