7 Specifications
7.1 Power-dependent Specifications
7.1.1 VLT
®
HVAC Drive FC 102
Power range
N315
N355
N400
N450
N500
Drive modules
2
2
2
2
2
Rectifier configuration
12-pulse
6-pulse/12-pulse
High/normal load
NO
NO
NO
NO
NO
Typical shaft output at 400 V [kW]
315
355
400
450
500
Typical shaft output at 460 V [hp]
450
500
600
600
700/650
Protection rating
IP00
Efficiency
0.98
Output frequency [Hz]
0–590
Heat sink overtemperature trip [
°
C (
°
F)]
110 (230)
Power card ambient trip [
°
C (
°
F)]
80 (176)
Output current [A]
Continuous (at 380–440 V)
588
658
745
800
880
Intermittent (60 s overload) at 400 V
647
724
820
880
968
Continuous (at 460/500 V)
535
590
678
730
780
Intermittent (60 s overload) at 460/500 V
588
649
746
803
858
Continuous (at 400 V) [kVA]
407
456
516
554
610
Continuous (at 460 V) [kVA]
426
470
540
582
621
Continuous (at 500 V) [kVA]
463
511
587
632
675
Input current [A]
Continuous (at 400 V)
567
647
733
787
875
Continuous (at 460/500 V)
516
580
667
718
759
Power losses [W]
Drive modules at 400 V
5825
6110
7069
7538
8468
Drive modules at 460 V
4998
5964
6175
6609
7140
AC busbars at 400 V
550
555
561
565
575
AC busbars at 460 V
548
551
556
560
563
DC busbars during regeneration
93
95
98
101
105
Maximum cable size [mm
2
(mcm)]
Mains
1)
4x120 (250)
4x150 (300)
Motor
4x120 (250)
4x150 (300)
Brake
4x70 (2/0)
4x95 (3/0)
Regeneration terminals
4x120 (250)
4x150 (300)
6x120 (250)
Maximum external mains fuses
6-pulse configuration
–
–
–
–
600 V, 1600 A
12-pulse configuration
700 A, 600 V
–
Table 7.1 FC 102, 380–480 V AC Mains Supply (2-module System)
1) For 12-pulse units, the cables between the star and delta terminals must be equal in number and length.