Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
50
53
54
55
42
39
130BB934.11
Function
Setting
Parameter 5-10 Terminal
18 Digital Input
[8] Start
Parameter 5-11 Terminal
19 Digital Input
[10]
Reversing*
Parameter 5-12 Terminal
27 Digital Input
[0] No
operation
Parameter 5-14 Terminal
32 Digital Input
[16] Preset
ref bit 0
Parameter 5-15 Terminal
33 Digital Input
[17] Preset
ref bit 1
Parameter 3-10 Preset
Reference
Preset ref. 0
Preset ref. 1
Preset ref. 2
Preset ref. 3
25%
50%
75%
100%
* = Default value
Notes/comments:
Table 5.12 Start/Stop with Reversing and 4 Preset Speeds
5.2.7 External Alarm Reset
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
130BB928.11
Function
Setting
Parameter 5-11 T
erminal 19
Digital Input
[1] Reset
* = Default value
Notes/comments:
Table 5.13 External Alarm Reset
5.2.8 Motor Thermistor
WARNING
THERMISTOR INSULATION
Risk of personal injury or equipment damage.
•
To meet PELV insulation requirements, use only
thermistors with reinforced or double
insulation.
Parameters
130BB686.12
VLT
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
50
53
54
55
42
39
A53
U - I
D IN
37
Function
Setting
Parameter 1-90
Motor Thermal
Protection
[2] Thermistor
trip
Parameter 1-93 T
hermistor
Resource
[1] Analog
input 53
* = Default value
Notes/comments:
If only a warning is needed, set
parameter 1-90 Motor Thermal
Protection
to
[1] Thermistor
warning
.
Table 5.14 Motor Thermistor
Application Set-up Examples
VLT
®
Parallel Drive Modules
28
Danfoss A/S © 08/2017 All rights reserved.
MG37L202
5