2.1.12 Value, Step-by-step
Certain parameters can be changed step-by-step. This
applies to
•
Parameter 1-20 Motor Power [kW]
,
•
•
Parameter 1-23 Motor Frequency
The parameters are changed both as a group of numeric
data values and as numeric data values that are infinitely
varying.
2.1.13 Read out and Programming of
Indexed Parameters
Parameters are indexed when placed in a rolling stack.
Parameter 15-30 Alarm Log: Error Code
to
parameter 15-33 Alarm Log: Date and Time
contain a fault
log which can be read out. Select a parameter, press [OK],
and use the [
▲
]/[
▼
] navigation keys to scroll through the
value log.
Use
parameter 3-10 Preset Reference
as another example:
Select the parameter, press [OK], and use the [
▲
]/[
▼
]
navigation keys to scroll through the indexed values. To
change the parameter value, select the indexed value and
press [OK]. Change the value by using the[
▲
]/[
▼
] keys.
Press [OK] to accept the new setting. Press [Cancel] to
abort. Press [Back] to leave the parameter.
2.1.14 Initialisation to Default Settings
Initialise the frequency converter to default settings in 2
ways.
Recommended initialisation (via
parameter 14-22 Operation Mode
)
1.
Select
parameter 14-22 Operation Mode
2.
Press [OK].
3.
Select [2] Initialisation.
4.
Press [OK].
5.
Cut off the mains supply and wait until the
display turns off.
6.
Reconnect the mains supply - the frequency
converter is now reset.
7.
Change
parameter 14-22 Operation Mode
back to
[0] Normal Operation
.
NOTICE
Resets parameters selected in Personal Menu with
default factory setting.
Parameter 14-22 Operation Mode
initialises all
except
Parameter 8-35 Minimum Response Delay
Parameter 8-36 Maximum Response Delay
Parameter 8-37 Maximum Inter-Char Delay
Parameter 15-00 Operating hours
to
Parameter 15-20 Historic Log: Event
to
parameter 15-22 Historic Log: Time
Parameter 15-30 Alarm Log: Error Code
to
parameter 15-32 Alarm Log: Time
Manual initialisation
1.
Disconnect from mains and wait until the display
turns off.
2.
2a
Press [Status] - [Main Menu] - [OK] at
the same time while power up for LCP
102, Graphical Display.
2b
Press [Menu] while power up for LCP
101, Numerical Display.
3.
Release the keys after 5 s.
4.
The frequency converter is now programmed
according to default settings.
This procedure initialises all except:
•
Parameter 15-00 Operating hours
;
•
;
•
•
NOTICE
Manual initialisation:
•
Resets serial communication.
•
Resets
and fault log
settings.
•
Removes parameters selected in
parameter 25-00 Cascade Controller
NOTICE
After initialisation and power cycling, the display does
not show any information until after a couple of minutes.
How to Programme
Programming Guide
MG11CE02
Danfoss A/S © 03/2015 All rights reserved.
23