16-56 Feedback 3 [Unit]
Range:
Function:
0
ProcessCtrlUnit
*
[-999999.999 -
999999.999
ProcessCtrlUnit]
View value of Feedback 3, see
parameter group 20-0*
Feedback
.
The value is limited by
settings in
parameter 20-13 Minimum
Reference/Feedb.
and
parameter 20-14 Maximum
Reference/Feedb.
. Units as set
in
20-12 Reference/Feedback
Unit
.
16-58 PID Output [%]
Range:
Function:
0 %
*
[0 - 100 %] This parameter returns the drive closed-loop
PID controller output value in percent.
3.16.5 16-6* Inputs and Outputs
16-60 Digital Input
Range:
Function:
0
*
[ 0 -
65535 ]
View the signal states from the active digital
inputs. Example: Input 18 corresponds to bit
number 5, 0=no signal, 1=connected signal. Bit 6
works in the opposite way, on=0, off=1 (safe
torque off input).
Bit 0
Digital input term. 33
Bit 1
Digital input term. 32
Bit 2
Digital input term. 29
Bit 3
Digital input term. 27
Bit 4
Digital input term. 19
Bit 5
Digital input term. 18
Bit 6
Digital input term. 37
Bit 7
Digital input GP I/O term. X30/4
Bit 8
Digital input GP I/O term. X30/3
Bit 9
Digital input GP I/O term. X30/2
Bit 10-63
Reserved for future terminals
Table 3.20 Active Digital Inputs
16-60 Digital Input
Range:
Function:
Illustration 3.44 Relay Settings
16-61 Terminal 53 Switch Setting
Option:
Function:
View the setting of input terminal 53.
[0]
*
Current
[1]
Voltage
16-62 Analog Input 53
Range:
Function:
0
*
[-20 - 20 ]
View the actual value at input 53.
16-63 Terminal 54 Switch Setting
Option:
Function:
View the setting of input terminal 54.
[0]
*
Current
[1]
Voltage
16-64 Analog Input 54
Range:
Function:
0
*
[-20 - 20 ]
View the actual value at input 54.
16-65 Analog Output 42 [mA]
Range:
Function:
0
*
[0 - 30 ] View the actual value at output 42 in mA. The
value shown reflects the selection in
parameter 6-50 Terminal 42 Output
16-66 Digital Output [bin]
Range:
Function:
0
*
[0 - 15 ]
View the binary value of all digital outputs.
16-67 Pulse Input #29 [Hz]
Range:
Function:
0
*
[0 - 130000 ] View the actual frequency rate on terminal 29.
Parameter Descriptions
Programming Guide
MG11CE02
Danfoss A/S © 03/2015 All rights reserved.
133