3.16 Main Menu - Application Functions 2 -
Group 24
3.16.1 24-0* Fire Mode
CAUTION
Please note the adjustable frequency drive is only one
component of the VLT HVAC Basic Drive system. Correct
function of Fire Mode depends on the correct design and
selection of system components. Ventilation systems
working in life safety applications have to be approved by
the local fire authorities.
Non-interruption of the adjustable
frequency drive due to Fire Mode operation could cause over
pressure and result in damage to VLT HVAC Basic Drive
system and components, including dampers and air ducts.
The adjustable frequency drive itself could be damaged and it
may cause damage or fire. Danfoss accepts no responsibility
for errors, malfunctions personal injury or any damage to the
adjustable frequency drive itself or components herein, VLT
HVAC Basic Drive systems and components herein or other
property when the adjustable frequency drive has been
programmed for Fire Mode. In no event shall Danfoss be
liable to the end user or any other party for any direct or
indirect, special or consequential damage or loss suffered by
such party, which has occurred due to the adjustable
frequency drive being programmed and operated in Fire
Mode.
Background
Fire Mode is for use in critical situations, where it is
imperative for the motor to keep running, regardless of
the adjustable frequency drive's normal protective
functions. These could be ventilation fans in tunnels or
stairwells for instance, where continued operation of the
fan facilitates safe evacuation of personnel in the event of
a fire. Some selections of Fire Mode Function cause alarms
and trip conditions to be disregarded, enabling the motor
to run without interruption.
Activation
Fire Mode is activated only via digital input terminals. See
parameter group 5-1* Digital Inputs.
Messages in display
When Fire Mode is activated, the display will show a status
message “Fire Mode” and a warning “Fire Mode”.
Once Fire Mode is again deactivated, the status messages
will disappear and the warning will be replaced by the
warning “Fire M Was Active”. This message can only be
reset by power-cycling the adjustable frequency drive
supply. If, while the adjustable frequency drive is active in
Fire Mode, a warranty-affecting alarm (see
24-09 FM Alarm
Handling
) should occur, the display will show the warning
“Fire M Limits Exceeded”.
Digital and relay outputs can be configured for the status
messages “Fire Mode Active” and the warning “Fire M Was
Active”. See parameter group5-3* and parameter group
5-4*.
“Fire M was Active” messages can also be accessed in the
warning word via serial communication. (See relevant
documentation).
The status messages “Fire Mode” can be accessed via the
extended status word.
Message
Type
LCP
Messages in display
Warning Word 2
Ext. Status Word 2
Fire Mode
Status
+
+
+ (bit 25)
Fire Mode
Warning
+
Table 3.13
Log
An overview of events related to Fire Mode can be viewed
in the Fire Mode log, parameter group 18-1*.
The log will include up to 10 of the latest events.
Warranty-affecting alarms will have a higher priority.
The log cannot be reset.
Following events are logged:
*Warranty affecting alarms (see
24-09 FM Alarm Handling
,
Fire Mode Alarm Handling)
*Fire Mode activated
All other alarms occurring while Fire Mode activated will
be logged as usual.
NOTE!
During Fire Mode operation all stop commands to the
adjustable frequency drive will be ignored, including
Coast/Coast inverse and External Interlock.
NOTE!
If setting the command
[11] Start Reversing
on a digital
input terminal in
5-10 Terminal 18 Digital Input
, the
adjustable frequency drive will understand this as a
reversing command.
Parameters
VLT
®
HVAC Basic Drive Programming Guide
3-62
MG18B222 - VLT
®
is a registered Danfoss trademark
3
3
Содержание VLT HVAC Drive FC 100 Series
Страница 1: ...MAKING MODERN LIVING POSSIBLE Programming Guide VLT HVAC Basic Drive ...
Страница 2: ......
Страница 14: ...Introduction VLT HVAC Basic Drive Programming Guide 1 8 MG18B222 VLT is a registered Danfoss trademark 1 1 ...
Страница 28: ...How to Program VLT HVAC Basic Drive Programming Guide 2 14 MG18B222 VLT is a registered Danfoss trademark 2 2 ...
Страница 100: ...Troubleshooting VLT HVAC Basic Drive Programming Guide 4 8 MG18B222 VLT is a registered Danfoss trademark 4 4 ...
Страница 116: ...Parameter Lists VLT HVAC Basic Drive Programming Guide 5 16 MG18B222 VLT is a registered Danfoss trademark 5 5 ...
Страница 121: ...Index VLT HVAC Basic Drive Programming Guide MG18B222 VLT is a registered Danfoss trademark 6 5 ...
Страница 122: ...www danfoss com drives MG18B222 130R0221 MG18B222 Rev 2012 10 22 ...