Aggressive environment (IEC 60721-3-3), non-coated enclosure sizes
I2–I8
Class 3C2
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature
(1)
See maximum output current at 40/50 °C (104/122 °F) in
.
Minimum ambient temperature during full-scale operation
0 °C (32 °F)
Minimum ambient temperature at reduced performance, enclosure
sizes H1–H5 and I2–I4
-20 °C (-4 °F)
Minimum ambient temperature at reduced performance, enclosure
sizes H6–H10 and I6–I8
-10 °C (14 °F)
Temperature during storage/transport
-30 to +65/70 °C (-22 to +149/158°F)
Maximum altitude above sea level without derating
1000 m (3281 ft)
Maximum altitude above sea level with derating
3000 m (9843 ft)
Derating for high altitude
6.3.2 Derating for Low Air Pressure and High Altitudes
.
Safety standards
EN/IEC 61800-5-1, UL 508C
EMC standards, Emission
EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EMC standards, Immunity
EN 61800-3, EN 61000-3-12, EN 61000-6-1/2, EN 61000-4-2, EN
61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
Energy efficiency class
(2)
IE2
1
Refer to Special Conditions in the design guide for:
•
Derating for high ambient temperature.
•
Derating for high altitude.
2
Determined according to EN 50598-2 at:
•
Rated load.
•
90% rated frequency.
•
Switching frequency factory setting.
•
Switching pattern factory setting.
Specifications
Operating Guide | VLT® HVAC Basic Drive FC 101
AQ275641848264en-000101 / 132R0078| 79
Danfoss A/S © 2019.11