5.1.3 Side-by-Side Installation
The frequency converter can be mounted side-by-side and requires the clearance above and below for cooling.
Power [kW]
Clearance above/below [mm/inch]
Frame
IP class
3x200-240 V
3x380-480 V
3x525-600 V
H1
IP20
0.25-1.5
0.37-1.5
100/4
H2
IP20
2.2
2.2-4
100/4
H3
IP20
3.7
5.5-7.5
100/4
H4
IP20
5.5-7.5
11-15
100/4
H5
IP20
11
18.5-22
100/4
H6
IP20
15-18.5
30-45
18.5-30
200/7.9
H7
IP20
22-30
55-75
37-55
200/7.9
H8
IP20
37-45
90
75-90
225/8.9
H9
IP20
2.2-7.5
100/4
H10
IP20
11-15
200/7.9
Table 5.4 Clearance
NOTICE
With IP21/Nema Type1 option kit mounted, a distance of 50 mm between the units is required.
5.1.4 Field Mounting
IP21/TYPE 1 kits are recommended.