14-64 Dead Time Compensation Zero Current Level
Default value: [0] Disabled
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: False
If a long motor cable is used, set the parameter to
[1] Enabled
to minimize the motor-torque ripple.
Table 262: Option:
[0]
Disabled
[1]
Enabled
14-65 Speed Derate Dead Time Compensation
Default value: Configuration dependent
Parameter type: Range
2-setup: All setups
Conversion index: 0
Data type: u_int16
Change during operation: False
Dead-time compensation level is reduced linearly from the maximum level of the output frequency set in
parameter 14-07 Dead
Time Compensation Level
to the minimum level of the output frequency set in this parameter.
Table 263: Range:
Min: 20 Hz
Max: 1000 Hz
Default value: Configuration dependent
4.11.8 14-9* Fault Settings
The parameter group for fault customization settings.
14-90 Fault Level
Default value: [3] Trip lock
Parameter type: Option
2-setup: 1 setup
Conversion index: -
Data type: u_int8
Change during operation: False
Use this parameter to customize fault levels. Only index 7, which indicates overcurrent faults, is supported.
Table 264: Option:
[3] Trip lock
Alarm is set to trip lock level.
[4] Trip w. delayed
reset
Alarm is configured into trip alarm, which can be reset after a delay time. For example, if overcurrent
alarm is configured to this option, it can be reset 3 minutes after the alarm is reported.
[5] Flystart
The drive tries to catch a motor spinning when starting. If this option is selected,
parameter 1-73 Flying
Start
is set to
[1] Enabled
.
4.12 Parameter Group 15-** Drive Information
Parameter group containing drive information such as operating data, hardware configuration, and software versions.
4.12.1 15-0* Operating Data
15-00 Operating hours
Default value: 0 h
Parameter type: Range
2-setup: 1 setup
Conversion index: -
Data type: u_int32
Change during operation: True
AU363928304090en-000101 / 130R0982
138 | Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111