Serial communication
500 Address
(BUS ADDRESS)
Value:
Parameter 500 Protocol = FC protocol [0]
0 - 247
✭
1
Parameter 500 Protocol = Metasys N2 [1]
1 - 255
✭
1
Parameter 500 Protocol = MODBUS RTU [3]
1 - 247
✭
1
Function:
This parameter allows the allocation of an
address to each frequency converter in a serial
communication network.
Description of choice:
The individual frequency converter must be
allocated a unique address.
If the number of units connected (frequency converters
+ master) is higher than 31, a repeater must be used.
Parameter 500
Address
cannot be selected
via the serial communication, but must be
preset via the control unit.
501 Baudrate
(BAUDRATE)
Value:
300 Baud (300 BAUD)
[0]
600 Baud (600 BAUD)
[1]
1200 Baud (1200 BAUD)
[2]
2400 Baud (2400 BAUD)
[3]
4800 Baud (4800 BAUD)
[4]
✭
9600 Baud (9600 BAUD)
[5]
Function:
This parameter is for programming the speed at which
data is transmitted via the serial port. Baud rate is
defined as the number of bits transmitted per second.
Description of choice:
The frequency converter
’
s transmission speed
must be set at a value corresponding to the
transmission speed of the master.
Parameter 501
Baudrate
cannot be selected via the
serial port, but must be preset via the operating unit.
502 Coasting Stop
(COASTING SELECT)
Value:
Digital input (DIGITAL INPUT)
[0]
Serial port (SERIAL PORT)
[1]
Logic and (LOGIC AND)
[2]
✭
Logic or (LOGIC OR)
[3]
Function:
Parameters 502-508 allow a choice between
controlling the frequency converter via the digital
inputs and/or via the serial port.
If
Serial port
[1] is selected, the relevant
command can only be activated if a command
is given via the serial port.
In the case of
Logic and
[2] the function must
also be activated via a digital input.
Description of choice:
The table below shows when the motor is running
and when it is coasting, when each of the
following is selected:
Digital input
[0],
Serial port
[1],
Logic and
[2] or
Logic or
[3].
NB!:
Note that
Coasting stop
and Bit 03 in the
control word are active at logic
’
0
’
.
Digital input
[0]
Dig. input
Ser. port
Function
0
0
Coasting
0
1
Coasting
1
0
Motor running
1
1
Motor running
Serial port
[1]
Dig. input
Ser. port
Function
0
0
Coasting
0
1
Motor running
1
0
Coasting
1
1
Motor running
Logic and
[2]
Dig. input
Ser. port
Function
0
0
Coasting
0
1
Motor running
1
0
Motor running
1
1
Motor running
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.04.B7.02 - VLT is a registered Danfoss trademark
88