8 Specifications
8.1 Electrical Data and Wire Sizes
8.1.1 Overview
Mains Supply 3x380-480 V AC
Frequency converter
PK37
PK55
PK75
P1K1
P1K5
P2K2
P3K0
Rated Shaft Output [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3.0
Rated Shaft Output [hp]
0.5
0.75
1.0
1.5
2.0
3.0
4.0
Max. input current
ON
WARNING
ALARM
Bus MS
NS2
NS1
130BB800.10
Continuous (3x380-440 V) [A]
1.2
1.6
2.2
2.7
3.7
5.0
6.5
Intermittent (3x380-440 V) [A]
1.9
2.6
3.5
4.3
5.9
8.0
10.4
Continuous (3x441-480 V) [A]
1.0
1.4
1.9
2.7
3.1
4.3
5.7
Intermittent (3x441-480 V) [A]
1.6
2.2
3.0
4.3
5.0
6.9
9.1
Recommended max. fuse size (non
UL)
gG-25
Built-in circuit breaker (large unit)
CTI-25M Danfoss part no.: 047B3151
Recommended circuit breaker
Danfoss CTI-25M (small and large
unit) part number:
0.37, 0.55 kW
Danfoss part no.: 047B3148
0.75, 1.1 kW
Danfoss part no.: 047B3149
1.5, 2.2 and 3 kW
Danfoss part no.: 047B3151
Recommended circuit breaker
Danfoss CTI-45MB
1)
(small unit) part
number:
0.55, 0.75 kW
Danfoss part no.: 047B3160
1.1 kW
Danfoss part no.: 047B3161
1.5 kW
Danfoss part no.: 047B3162
2.2 kW
Danfoss part no.: 047B3163
Power loss at max. load [W]
2)
35
42
46
58
62
88
116
Efficiency
3)
0.93
0.95
0.96
0.96
0.97
0.97
0.97
Weight, small unit [kg]
9.8
N/A
Weight, large unit [kg]
13.9
Output current
ON
WARNING
ALARM
Bus MS
NS2
NS1
130BB799.10
Continuous (3x380-440 V) [A]
1.3
1.8
2.4
3.0
4.1
5.2
7.2
Intermittent (3x380-440 V) [A]
2.1
2.9
3.8
4.8
6.6
8.3
11.5
Continuous (3x441-480 V) [A]
1.2
1.6
2.1
3.0
3.4
4.8
6.3
Intermittent (3x441-480 V) [A]
1.9
2.6
3.4
4.8
5.4
7.7
10.1
Continuous kVA (400 V AC) [kVA]
0.9
1.3
1.7
2.1
2.8
3.9
5.0
Continuous kVA (460 V AC) [kVA]
0.9
1.3
1.7
2.4
2.7
3.8
5.0
Max. cable size: (mains, motor,
brake) [mm
2
/AWG]
solid cable 6/10
flexible cable 4/12
Table 8.1 FCD 302 Shaft Output, Output Current and Input Current
1) Type CTI-45MB circuit breakers are not available for 3 kW units.
2) Applies for dimensioning of frequency converter cooling. If the
switching frequency is higher than the default setting, the power
losses may increase. LCP and typical control card power
consumptions are included. For power loss data according to EN
50598-2, refer to www.danfoss.com/vltenergyefficiency.
3) Efficiency measured at nominal current. For energy efficiency class,
see chapter 8.2 General Specifications. For part load losses see
www.danfoss.com/vltenergyefficiency.