11.2.14 Gate Drive Card
To remove or replace the gate drive card, use the following steps. Refer to
Disassembly
1.
Remove the AC input busbars or RFI option (not
shown). Refer to
chapter 11.2.5 AC Input Busbars
.
2.
Unplug the cables from the following gate drive
card connectors:
2a
MK100
2b
MK102
2c
MK201, if brake option is present
2d
MK501
2e
MK601
2f
MK701
3.
Remove 6 thread-forming screws (T20) from the
gate drive card. Remove the card from the unit.
Reassembly
Tighten hardware according to
.
1.
Position the gate drive card in the unit.
2.
Fasten 6 thread-forming screws (T20) in the gate
drive card.
3.
Plug the cables into the following gate drive card
connectors:
3a
MK100
3b
MK102
3c
MK201, if brake option is present
3d
MK501
3e
MK601
3f
MK701
4.
Replace the AC input busbars or RFI option (not
shown). Refer to
chapter 11.2.5 AC Input Busbars
D2h/D4h/D7h/D8h/J9 Unit Dis...
Service Guide
MG94A502
Danfoss A/S © 02/2019 All rights reserved.
205
11
11