10.2.19 IGBTs
Disassembly in 240/400 V AC units
1.
Remove the gate drive card. Refer to
chapter 10.2.17 Gate Drive Card
.
2.
Remove the SCR input busbars. Refer to
chapter 10.2.15 SCR Input Busbars
3.
Remove the balance/high frequency card. Refer to
chapter 10.2.12 Balance/High Frequency Card
.
4.
Remove the insulation sheet from the capacitor
bank.
5.
Remove the cylinder busbar support bracket by
removing 3 screws (T30).
6.
Remove 1 thread-forming screw (T25) from each
IGBT output busbar.
7.
Remove the IGBT output busbar by removing 2
screws (T30), from each IGBT output busbar.
8.
Disconnect the IGBT temperature cable from each
IGBT module.
9.
Remove the gate leads, 1 from each IGBT module.
10.
Remove the snubber capacitor from each IGBT
module by removing 2 screws (T30).
11.
To remove the DC(-) plate:
11a
Remove 3 screws (T20) next to the IGBT
modules.
11b
Unfasten 1 standoff (8 mm) connecting
the plate to the negative terminal of
capacitor 3.
11c
Remove the screws (T25) connecting the
plate to the negative terminals of
capacitors 4 and 5. The number of
screws varies based on drive size.
12.
Remove the insulator sheet between the DC(-)
plate and the DC(+) and midplate.
13.
To remove the DC(+) plate:
13a
Remove 3 screws (T20).
13b
Unfasten 1 standoff (8 mm) connecting
the plate to the positive terminal of
capacitor 2.
13c
Remove the screws (T25) connecting the
plate to the positive terminals of
capacitors 1 and 6. The number of
screws varies based on drive size.
14.
Remove the plastic IGBT support (not shown) by
removing 4 screws (T25).
15.
Remove the IGBTs by removing 4 screws (T25)
from each IGBT.
Disassembly in 690 V AC units
1.
Remove the gate drive card. Refer to
chapter 10.2.17 Gate Drive Card
2.
Remove the SCR input busbars. Refer to
chapter 10.2.15 SCR Input Busbars
.
3.
Remove the balance/high frequency card. Refer to
chapter 10.2.12 Balance/High Frequency Card
4.
Remove the insulation sheet from the capacitor
bank.
5.
Remove the cylinder busbar support bracket by
removing 3 screws (T30).
6.
Remove 1 thread-forming screw (T25) from each
IGBT output busbar.
7.
Remove the IGBT output busbar by removing 2
screws (T30) from each IGBT output busbar.
8.
Disconnect the IGBT temperature cable from each
IGBT module.
9.
Remove the gate leads, 1 from each IGBT.
10.
Remove the snubber capacitor from each IGBT
module by removing 2 screws (T30).
11.
To remove the DC(-) plate:
11a
Remove 3 screws (T20 thread-forming)
next to the IGBT modules.
11b
Remove 1 standoff (8 mm) connecting
the plate to the negative terminal of
capacitor 1.
11c
Remove 1 screw (T25) from the negative
terminal of capacitor 3.
11d
Remove 1 round plastic alignment cap.
12.
Remove the insulator sheet between the DC(-)
plate and the DC(+) plate.
13.
To remove the DC(+) plate:
13a
Remove 3 thread-forming screws (T20).
13b
Remove 2 screws (T25) connecting the
plate to the positive terminals of
capacitors 5 and 6.
14.
Remove the plastic IGBT support (not shown) by
removing 4 screws (T25).
15.
Remove the IGBTs by removing 4 screws (T25)
from each.
Reassembly
For reassembly, use the replacement IGBT instructions.
D1h/D3h/D5h/D6h/J8 Drive Di...
VLT
®
FC Series, D1h–D8h, Da2/Db2/Da4/Db4, E1h–E4h, J8/J9
154
Danfoss A/S © 02/2019 All rights reserved.
MG94A502
10
10
Содержание VLT FC Series
Страница 2: ......
Страница 369: ...Index Service Guide MG94A502 Danfoss A S 02 2019 All rights reserved 367...