Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
12
13
18
19
20
27
29
32
33
37
e30bb804.12
Function
Setting
Parameter 5-10 Termin
al 18 Digital Input
[8] Start*
Parameter 5-12 Termin
al 27 Digital Input
[19]
Freeze
Reference
Parameter 5-13 Termin
al 29 Digital Input
[21]
Speed Up
Parameter 5-14 Termin
al 32 Digital Input
[22]
Speed
Down
* = Default value
Notes/comments:
Table 7.4 Speed Up/Speed Down
130BB840.12
Speed
Reference
Start (18)
Freeze ref (27)
Speed up (29)
Speed down (32)
Illustration 7.1 Speed Up/Speed Down
7.2 Wiring for Start/Stop
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
130BB802.10
Function
Setting
Parameter 5-10
Terminal 18
Digital Input
[8] Start*
Parameter 5-12
Terminal 27
Digital Input
[0] No
operation
Parameter 5-19
Terminal 37 Safe
Stop
[1] Safe Stop
Alarm
* = Default value
Notes/comments:
If
parameter 5-12 Terminal 27
Digital Input
is set to
[0] No
operation
, a jumper wire to
terminal 27 is not needed.
Table 7.5 Start/Stop Command with Safe Torque Off Option
130BB805.12
Speed
Start/Stop (18)
Illustration 7.2 Start/Stop Command with Safe Torque Off
Wiring Configuration Exampl...
VLT® Refrigeration Drive FC 103
58
Danfoss A/S © 04/2018 All rights reserved.
MG16P222
7