4.3.4 SLC Application Example
2 sec
Max. ref.
P 3-03
2 sec
Preset ref.(0)
P 3-10(0)
State 1
State 3
State 2
Preset ref.(1)
P 3-10(1)
Term 18
P 5-10(start)
130BA157.11
State 1
Start and ramp up.
State 2
Run at reference speed for 2 s.
State 3
Ramp down and hold shaft until stop.
Illustration 4.12 Example of a Sequence
1.
Set the ramping times in
parameter 3-41 Ramp 1
Ramp Up Time
and
parameter 3-42 Ramp 1 Ramp
Down Time
to the wanted times
t
ramp
=
t
acc
× n
norm
par . 1 − 25
ref RPM
2.
Set terminal 27 to
[0] No Operation
(
parameter 5-12 Terminal 27 Digital Input
).
3.
Set preset reference 0 to the first preset speed
(
parameter 3-10 Preset Reference
[0]) in percentage
of maximum reference speed
(
parameter 3-03 Maximum Reference
). For example:
60%.
4.
Set preset reference 1 to the second preset speed
(
parameter 3-10 Preset Reference
[1] For example:
0% (zero).
5.
Set the timer 0 for constant running speed in
parameter 13-20 SL Controller Timer
[0]. For
example: 2 s.
6.
Set event 1 in
parameter 13-51 SL Controller Event
to
[1] True
.
7.
Set event 2 in
parameter 13-51 SL Controller Event
to
[4] On Reference
.
8.
Set event 3 in
parameter 13-51 SL Controller Event
to
[30] Time Out 0
.
9.
Set event 4 in
parameter 13-51 SL Controller Event
to
[0] False
.
10.
Set action 1 in
parameter 13-52 SL Controller
Action
to
[10] Select preset 0
.
11.
Set action 2 in
parameter 13-52 SL Controller
Action
to
[29] Start Timer 0
.
12.
Set action 3 in
parameter 13-52 SL Controller
Action
to
[11] Select preset 1
.
13.
Set action 4 in
parameter 13-52 SL Controller
Action
to
[1] No Action
.
14.
Set the smart logic control in
parameter 13-00 SL
Controller Mode
to
[1] ON
.
Start/stop command is applied on terminal 18. If a stop
signal is applied, the frequency converter ramps down and
enters free mode.
Application Examples
Design Guide
MG03M202
Danfoss A/S © 06/2016 All rights reserved.