6.3 Mains Supply
Mains supply (L1, L2, L3)
Supply voltage
380-480 V
±
10%
Mains voltage low/mains drop-out:
•
During low mains voltage or a mains drop-out, the frequency converter continues until the intermediate circuit
voltage drops below the minimum stop level, which corresponds typically to 15% below the lowest rated supply
voltage of the frequency converter. Power-up and full torque cannot be expected at mains voltage lower than 10%
below the lowest rated supply voltage of the frequency converter.
Supply frequency
50/60 Hz
Max. imbalance temporary between mains phases
3.0% of rated supply voltage
True Power Factor (
λ
)
≥
0.9 nominal at rated load
Displacement Power Factor (cos
φ
)
near unity (>0.98)
Switching on the input supply L1, L2, L3 (power-ups)
Max. 2 times/min.
Environment according to EN 60664-1
overvoltage category III/pollution degree 2
The unit is suitable for use on a circuit capable of delivering not more than
•
100,000 RMS symmetrical Amperes, 480 V maximum, with fuses used as branch circuit protection
•
10,000 RMS symmetrical Amperes, 480 V maximum, with circuit breakers used as branch circuit protection
6.4 Protection and Features
Protection and features
•
Electronic thermal motor protection against overload.
•
Temperature monitoring of the heat sink ensures that the frequency converter trips when the temperature reaches
90
°
C
±
5
°
C. An overload temperature cannot be reset until the temperature of the heatsink is below 70
°
C
±
5
°
C
(Guideline - these temperatures may vary for different power sizes, enclosures etc.). The frequency converter auto
derating function ensures that the heatsink temperature does not reach 90
°
C.
•
The frequency converter is protected against short-circuits between motor terminals U, V, W.
•
When a motor phase is missing, the frequency converter trips and issues an alarm.
•
When a mains phase is missing, the frequency converter trips or issues a warning (depending on the load).
•
Monitoring of the intermediate circuit voltage ensures that the frequency converter trips, when the intermediate
circuit voltage is too low or too high.
•
The frequency converter is protected against earth faults on motor terminals U, V, W.
•
All control terminals and relay terminals 01-03/04-06 comply with PELV (Protective Extra Low Voltage). However
this does not apply to grounded Delta leg above 400 V.
6.5 Ambient Conditions
Environment
Enclosure
IP66/Type 4X
Stationary vibration (IEC 60721-3-3 Class 3M6)
2.0 g
Non-stationary vibration (IEC 60721-3-3 Class 3M6)
25.0 g
Relative humidity (IEC 60721-3-3; Class 3K4 (non-condensing))
5%-95% during operation
Aggressive environment (IEC 60721-3-3)
Class 3C3
Test method according to IEC 60068-2-43
H2S (10 days)
Ambient temperature
40 °C (24-hour average)
Minimum ambient temperature during full-scale operation
-10
°
C
Minimum ambient temperature at reduced performance
-20
°
C
Temperature during storage
-25 to +65
°
C
Temperature during transport
-25 to +70
°
C